ADLINK ND-6024 User Manual

Page 40

Advertising
background image

34

Command Set

The command sets the analog output to be 4 mA at address 08H, if the
data format is configured as % of FSR and 0~20mA output range.

4mA = 20mA x 20.00%

User command:

#097FF<CR>

Response:

><CR>

The command sets the analog output to be 5 V at address 09H, if the data
format is configured as hexdecimal format and output range of 0~10V.

5 V = 7FF / FFF x 10V

User command:

#08A-05.000<CR>

Response:

><CR>

The command sets the analog output port A to be –5 V at address 08H.

Advertising