Analog Output Calibration

57

4. Send the “Analog Data Output #(Addr)(OutData)” command with

output value is 4 mA. For example if the address is 0x03 then

the

command is

#0304.000.

5. Use

Trim calibration $(Addr)3(Counts)” command to adjust until the

output value to 1 V (4 mA).

6. Send

4mA Calibration $(Addr)0” command to the analog output

module to complete the 4 mA calibration.

7. Send the “Analog Data Output #(Addr)(OutData)” command with

output value is 20 mA. For example if the address is 0x03 then the
command is

#0320.000

8. Use

Trim calibration $(Addr)3(Counts)” command to adjust until the

output value to 5 V (20 mA).

9. Send

20mA Calibration $(Addr)1” command to the analog output

module to complete the 20 mA calibration.

-IOUT

Calibration wiring of NuDAM-6021

+IOUT

250 Ohms

5 1/2 Digital Meter

+

-