12 model features, 1 logix 505, 2 logix 510 – Flowserve 500+ Series Logix User Manual

Page 40: 3 logix 520md, 4 md+ positioner diagnostic levels, 5 valvesight dtm diagnostic levels, Model features, Ogix, 520md, Ositioner

Advertising
background image

User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13

flowserve.com

40


12 MODEL FEATURES


12.1 Logix 505+

The Logix 505+ digital positioner includes –

the QUICK-CAL feature that allows the positioner to be
calibrated at the push of one button.

limited diagnostics that monitor position, the pilot relay
and electronics.

a 4-DIP configuration switch includes air action, split
range options and a gain adjustment.

12.2 Logix 510+


The Logix 510+ digital positioner includes –

an 8-DIP configuration switch for flexible set-up.

a 10-position gain selector switch is also included for
quick adjustments to responsiveness.

an LCD option provides a dashboard for viewing current
status and a complete menu for viewing and configuring
detailed settings.

up to two auxiliary cards for analog output (AO), discrete
input (DI) and discrete output (DO) functions.

12.3 Logix 520MD+

The Logix 520MD+ digital positioners include –

HART communication.

a DTM for viewing and controlling advanced features.

Additional diagnostics depending on the diagnostic level
chosen.

12.4 MD+ Positioner Diagnostic Levels

The Logix 520MD+ digital positioners have three levels of
diagnostics, “Standard”, “Advanced”, and “Pro”.

Standard” diagnostics provide complete safety and
position-related diagnostics and data.

Advanced” diagnostics provide additional pressure
data.

Pro” diagnostics enhance the off-line tests with
additional force data, and provide powerful on-line
monitoring capabilities including friction, data logging
functions, and comprehensive system health
information.

12.5 Valvesight DTM Diagnostic Levels


The DTM is not required for the positioner to function, but the
graphical capabilities of the DTM allow for a richer interface
and additional functionality, including viewing the dashboard,
charts, annunciator panel, test comparisons, and data logs
and printing reports.

The DTM also comes in two versions: “Basic” and
“Advanced”.

The “Basic” DTM provides an intuitive, easy-to-use user
interface to the positioner. It includes calibration,
configuration, auxiliary card information and off-line
diagnostic tests. A dashboard gives a quick view of
important information.

The “Advanced” DTM provides a view of the positioner’s
full health analysis and interfaces to all of the
positioner’s “Pro” diagnostic functionality.


It is generally wise to use the Advanced DTM with the
Advanced and Pro positioners.



Table 15: Logix 500+ and ValveSight DTM Features

DTM

Positioner

V

al

v

eS

ight

B

as

ic

V

al

v

eS

ight

A

dv

anc

ed

Logi

x

50

5+

Logi

x

51

0+

Logi

x

52

0M

D

+

(

S

tand

ar

d)

Logi

x

52

1M

D

+

(

A

dv

a

nc

ed)

Logi

x

52

2M

D

+

(

P

ro)

Hardware

Quick Calibration Button

X X X X X

3-LED Indicator

X X X X X

4-DIP Configuration

X

8-DIP Configuration

X X X X

10-Position Gain Adjustment Switch

X X X X

LCD Display Option

X X X X

Auxiliary Cards (AO, DO, DI)

X X X X

Pressure Sensors

X X X

On Board Clock

X X X

Humidity Sensor

X X X

Software

HART Communication

X X

X X X

Off-Line Diagnostics
(Ramp Test, Step Test, HDRL, Partial
Stroke Test)

X X

X X X

Data Monitor

(Monitor and Save Sensor Data)

X X

X X X

Pressure Sensor Data

(Supply, Port A, Port B)

X X

X X

Pro Diagnostics
(Force, Actuation, Pneumatic Leak,
Continuous Stroke Testing, etc.)

X

X

Health Evaluation
(Valve, Positioner, Actuator and
Control)

X

X

Training
(Determines Typical Behavior)

X

X

Data Logging
(High Speed Internal Data Capture)

X

X

Long-Term Trend Logging
(14 parameters over 15 years)

X

X



Advertising