7 limit switch specifications, 8 positioner performance characteristics, 9 physical specifications – Flowserve 500+ Series Logix User Manual

Page 9: 10 temperature, 11 valvesight dtm software specifications, Imit, Witch, Pecifications, Ositioner, Erformance

Advertising
background image

User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13

flowserve.com

9


2.7

Limit Switch Specifications

Table 7: Limit Switch Specifications

For entity parameters, see section 3 HAZARDOUS AREA
CERTIFICATIONS.

Switch

Specifications

Mechanical
Cherry DG 13-B(X)RA
NO and/or NC

General Purpose Only

Load Current:

3/2 AAC/ADC

Voltage:

125/30 VAC/VDC

Temperature:

-25 to +85 °C

(-13 °F to 185 °F)

Reed
Hamlin 59050-030
NO

Load Current: 500 mA
Voltage:

200VDC

Temperature:

-40 to +105 °C

(-40 °F to 221 °F)

Inductive Sensor
P&F NJ2-V3-N
NAMUR NC -3

Load Current:

Plate: ≤ 1 mA;

No Pla

te: ≥ 3 mA

Voltage:

Nominal 8.2 VDC

Temperature:

-25 °C to 100 °C

(-13 °F to 212 °F)

Inductive Proximity
P&F SJ2-S1N
NAMUR NO-4

Load Current:

Plate: ≤ 1 mA;

No Plate: ≥ 3 mA

Voltage:

5-25 VDC

(Nominal 8 VDC)

Temperature:

-25 °C to 100 °C

(-13 °F to 212 °F)

Inductive Proximity
P&F SJ2-SN
NAMUR NC-5

Load Current:

Plate: ≤ 1 mA;

No Plate: ≥ 3 mA

Voltage:

5-25 VDC

(Nominal 8 VDC)

Temperature:

-40 °C to 100 °C

(-40 °F to 212 °F)

Inductive Sensor
P&F NBB2-V3-E2
PNP NO

General Purpose Only

Load Current:

0…100 mA

Voltage:

10...30 VDC

Temperature:

-25 °C to 70 °C

(-13 °F to 158 °F)


2.8

Positioner Performance
Characteristics

Table 8: Performance Characteristics

Better than or equal to the following values on a 25 square inch
Mark I actuator.

Resolution

≤ 0.25%

Linearity

+/-1.25%

Repeatability

≤ 0.25%

Hysteresis

≤ 1.0%

Deadband

≤ 0.3%

Sensitivity

≤ 0.25%

Stability

≤ 0.4%

Long term drift

≤ 0.5%

Supply Pressure Effect

≤ 0.2%

NOTE: Performance tested according to ISA 75.13.












2.9

Physical Specifications

Table 9: Physical Specifications

For dimensions, see section 19 POSITIONER .

Housing Material

Cast, powder-painted aluminum

EN AC-AlSi12(Fe)

Soft Goods

Fluorosilicone

Weight of Base
Positioner Without
Accessories

With Single Acting Relay

1.76 kg (3,88 lb)

With Double Acting Relay

1.88 kg (4.14 lb)


2.10 Temperature

Table 10: Temperature

Operating Temperature
Range

-52 to 85°C (-61.6 to 185°F)

Transport and Storage
Range

-52 to 85°C (-61.6 to 185°F)

NOTE: Reduced performance possible at low

temperatures.

2.11 ValveSight DTM Software

Specifications

Table 11: ValveSight DTM Software Specifications

Computer

Minimum Pentium processor running
Windows 95, 98, NT, 2000, XP, 7, 32 MB
total memory (64 MB recommended), 30
MB available hard disk space, CD-ROM
drive

Ports

1 minimum available with 8 maximum
possible. (Can also communicate via
serial, PCMCIA and USB connections)

HART Modem

RS-232,

PCMCIA card, or

USB

HART Filter

May be required in conjunction with some
DCS hardware.

HART MUX

MTL 4840/ELCON 2700

Advertising