Rryg, Rryy, Rryr – Flowserve 500+ Series Logix User Manual

Page 58: Rrry

Advertising
background image

User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13

flowserve.com

58


galling of the trim or stem, excessively tightened packing,
linkages, or other valve or actuator mechanical issues.

Possible Solutions: Determine if the friction is significantly
interfering with the valve control. If not, consider increasing
the friction warning limit. Consider the following to reduce
friction: Stroke the valve to clear off build-up. Clear any
external mechanical obstruction, loosen the packing, clean
the stem, repair or replace the actuator. Highly localized
friction or very jerky travel can indicate internal galling.
Repair or replace internal valve components.

RRYG

●●

FEEDBACK LINKAGE ALARM

Description:

The feedback linkage is broken or the position

feedback POT is out of range.

Possible Solutions:

Fix broken linkage or adjust feedback

arm until full motion is within the range of the POT.

RRYY

●●

●●

BACKLASH ALARM

Description: The amount of detected backlash has passed
the user set alarm limit. This may affect valve stability.

Possible Solutions: Check the stem and actuator for loose
components.

RRYR

●●

DRIVER MODULE ALARM

Description: The pilot relay can't open, the pilot relay can't
shut, or the Hall sensor circuit has failed.

Possible Solutions: Check the internal wiring connections.
Replace the pilot relay.

RRRY

●●●

PIEZO VOLTAGE HIGH ALARM

Description: The voltage driving the piezo is above the alarm
limit. This could indicate an error with the relay or the main
board. The positioner may still be functioning, but have
reduced performance under some circumstances.

PIEZO VOLTAGE LOW ALARM

Description: The voltage to the piezo is too low. The piezo
may be damaged. This may prevent the proper failure
position upon loss of signal/power. This condition may occur
briefly on an air-to-close valve that is held for long periods of
time in the closed position, or an air-to-open valve held in the
open position.

Possible Solutions: Ensure the supply pressure is not low. If
alarm persists for more than 30 minutes, the Piezo assembly
is damaged. Replace the pilot relay.

RRRR

●●●●

POSITION DEVIATION ALARM

Description: The difference between the command and the
actual position has been greater than the user-set limit for
longer than a user-set time.

Possible Solutions: Review active alarms and warnings to
find root causes of this alarm. The deviation settings can be
changed in the Valve Health page of the DTM.