Direct mount on underground tanks – Gasboy 70 Series User Manual

Page 13

Advertising
background image

Installation

MDE-4423B Series 70 and 1800 Consumer Elect Pumps Installation/Operation/Parts

July 2005

2-5

Direct Mount on Underground Tanks

1.

Screw 2-inch coupling onto 2-inch standard pipe.


2.

Screw 2-inch standard pipe into 2-inch tank flange. Apply compound to threads at bottom of
base to prevent surface water from entering the tank.


3.

Screw 1-inch suction pipe into install-a-socket. Suction pipe should be long enough to allow
3-inch clearance from bottom of tank. Apply gasoline-resistant pipe compound to male
threads.


4. Lower 1-inch suction pipe through 2-inch standard pipe into tank. Tighten install-a-socket

into coupling at top of standard pipe.


5.

Screw pump (2-inch threaded base) into install-a-socket. This is a suction line connection
and must be tight. Apply gasoline-resistant pipe compound to male threads.


See

the

Conduit section for correct installation of electrical conduit.

Advertising