MDE-5067 FedEx Islander PLUS FMS Installation Manual · March 2013

Page 4-19

Pump Configuration

SiteOmat Software Set Up

5

In the Specific section, verify the following is set up for the installed pumps

(see

Figure 4-31

on

page 4-18

).

• Pulser Type - Select Half Cycle Count Pulse from the drop-down list.
• Pulse Factor - Enter the correct setting for the installed pumps (as 10 or 100).

- 10 - 10:1 Pulser on PUMP
- 100 - 100:1 Pulser on PUMP

• Virtual In Use - Select Enable when a handle switch is not available and select Disable at

all other times.
- This is always required for hose reels for oil and lubricants.
- This is required for some dispensers (PMC Pumps) without proper handle-switch wires.

• Flow Protection timeout - Set this to 70 seconds.

Note: Flow protection timeout controls the active time (70 seconds) of the Virtual In Use

after pulses stop.

6

Repeat steps

1

(on

page 4-17

) to

5

for all pumps and oil reels.

7

To save the pump configuration settings, click Save, the Setup screen appears.

Figure 4-32: Saving Pump Configuration

8

In the Setup screen, click Save (see

Figure 4-32

).

9

To load new configuration changes into the system, click Reload, a pop-up box appears as
shown in

Figure 4-33

(i)

.

10

Click OK when reloading is complete [see

Figure 4-33

(ii)

].

Figure 4-33: Reloading Configuration

(i)

(ii)

The More Options button is not used for FedEx Islander PLUS FMS installations.