Product Overview

Functional description
The water tank is filled up to a preset upper level via the level-controlled inlet solenoid valve (NC). When

the water level in the water tank drops below a certain limit, the level-controlled inlet solenoid valve opens

until the upper limit is reached again.
The Nortec ME Control provides On/Off or stage control by means of the Nortec ME Control control unit

and the stage pumps. The Nortec ME Control control unit processes analog sensor/control signals and

uses them to control the stage pumps.
In case of a humidification/cooling request with

activated On/Off control the inlet solenoid valve (NC)

opens and all stage pumps start and the water flows to the distribution header above the evaporative

cassettes.
In case of a humidification/cooling request with

activated stage control the inlet solenoid valve (NC)

opens, then one, two, three, four or all five stage pumps start (depending on the demand signal and

evaporative module size) and the water flows to the distribution header above the evaporative cassettes.
The distribution pipes inside the distribution header evenly supply the water to the entire surface of the

evaporative cassettes where it flows down and humidifies the air flowing through the evaporative cas-

settes. The excess water not used for humidification flows to the water tank.
To prevent accumulation of mineral residues and the formation of germs in the water tank, the tank is

completely drained periodically (interval or time controlled). Additionally further hygiene functions can

be activated: Operation-dependent draining of the water tank (fill cycle, conductivity, temperature or

time controlled).