Nortec ME Control User Manual

Page 53

Advertising
background image

53

Maintenance

Operations

Minor

Service

Complete

System Service

Replace all feed hose

–––

Yes

Check distribution headers

Yes

Yes

Clean distribution headers

–––

Yes

Clean pumps

–––

Yes

Clean front section of tank

Yes

Yes

Clean internal of hydraulic module (use soft cloth only)

Yes

Yes

Check operation of level float and conductivity sensor (if applic able)

Yes

Yes

Clean level float and conductivity sensor

–––

Yes

Check droplet separator (if applicable) and evaporator cassettes in suit-

able condition

Yes

Yes

Lightly brush evaporator cassettes if necessary, replace if heavily soiled

–––

Yes

Remove evaporator cassettes and clean all sections of tank and frame

structure

–––

Yes

Check and secure frame structure and seal

–––

Yes

Run unit and check for correct water level

Yes

Yes

Check all media for full saturation

Yes

Yes

Check drain pump operation and correct flow

Yes

Yes

Check operation of all distribution pumps

Yes

Yes

Measure flow rates to distribution headers

–––

Yes

Check water temperature and conductivity is within calibration

Yes

Yes

Check and secure all electrical connections

Yes

Yes

Check overall installation for leaks and damage

Yes

Yes

Check software settings

Yes

Yes

Check operation of submerged UV lamps

Yes

Yes

Replace UV kits

–––

Yes

Check any options as per relevant documentation

Yes

Yes

Complete disinfection as described in this manual

Yes

Yes

Check safety interlock and humidity/temperature control devices

–––

Yes

Check air velocity at face of evaporative cassettes matrix

–––

Yes

Reset all appropriate maintenance counters

Yes

Yes

Update service log book

Yes

Yes

Add DISIFIN XL disinfection sachet(s) to tank

Yes

Yes