Nortec ME Control User Manual

Page 66

Advertising
background image

66 Fault elimination

Code

Message

Information

Warning

Fault

Possible causes

Remedy

–––

E50

Out of

Commissioning

The water held in the supply pipework needs to be fully drained. Any contact with

the Nortec ME Control has to be avoided.
Nortec ME Control not energised for more

than 48 hours.

Disconnect water supply pipe and flush

supply pipe. Reconnect water supply

pipe and manually flush the entire water

system.

–––

E51

Dosing Level

Level in the liquid tank of the optional system for enhancing polyester media water

absorbtion too low. Current operation status not affected.
Liquid used up during normal operation. Refill liquid.
Incorrect floater connection.

Check/correctly connect floater.

Floater defective.

Replace floater sensor.

–––

E54

Standing WTR

Standing water outside the tank detected. The Nortec ME Control stopped operating

as a leak of the tank or pipework has been detected.
Water leakage on evaporative module or

water piping inside the duct.

Check system and seal any leaky com-

ponents.

–––

E55

Ag+ Service

PureFlo Ag+ silver ion cartridge replacement interval exceeded, current operation

status not affected.
Lifespan of PureFlo Ag+ silver ion car-

tridge exceeded.

Replace PureFlo Ag+ silver ion cartridge.

PureFlo Ag+ silver ion cartridge replace-

ment interval counter not reset after

replacement of cartridge.

Reset PureFlo Ag+ silver ion cartridge

replacement interval counter.

–––

E57

Activation

Activation code not yet entered. Normal operation not possible.
Activation code not yet entered.

Enter activation code.

–––

E70

Water Condu

Snsr

Water conductivity sensor signal failed, Nortec ME Control changed to “Fill Cycle”

mode dilution. The fault message must be reset after elimination of malfunction.
Water conductivity sensor not connected. Correctly connect water conductivity

sensor.

Incorrect water conductivity sensor con-

figuration.

Contact your Nortec representative.

Water conductivity sensor defective.

Replace water conductivity sensor.

–––

E74

Keep Alive

Faulty communication, Nortec ME Control automatically stopped operation. The

fault message must be reset after elimination of malfunction.
Driver board not connected.

Correctly connect driver board.

Wrong driver board connected.

Connect correct driver board.

Driver board defective.

Replace driver board.

–––

E82

Driver Missing

Communication with driver board failed, Nortec ME Control automatically stopped

operation. The fault message must be reset after elimination of malfunction.
RS485 Bus to driver board interrupted. Contact your Nortec representative.

–––

E83

Slave Address

Slave address changed during operation, Nortec ME Control automatically stopped

operation. The fault message must be reset after elimination of malfunction.
Wrong driver address.

Check that each driver board connected

to one controller has a different address.

–––

E84

Driver faulty

Unspecific driver board fault, Nortec ME Control automatically stopped operation.

The fault message must be reset after elimination of malfunction.
Driver board defective.

Replace driver board.

–––

E85

Driver ID Wrong Driver board ID wrong, Nortec ME Control automatically stopped operation. The

fault message must be reset after elimination of malfunction.
Wrong driver board connected or SAB

address wrong.

Contact your Nortec representative.

Advertising