9 cleaning and disinfection method statement, Cleaning and disinfection method statement – Nortec ME Control User Manual

Page 58

Advertising
background image

58 Maintenance

Recommended disinfection equipment

– Disinfection solution in accordance with manufacturers guidelines.

– Disinfection neutraliser (only if necessary).

– Disinfection solution test kit (to measure strength).

– Bucket of fresh water.

– Cleaning equipment.

– Mixing vessel / Measuring container.

– Risk assessment / test record sheets. Appropriate report/record

– Standard tools

– Appropriate PPE

– COSHH risk assessment / MSDS

6.9

Cleaning and disinfection method statement

Step 1 - Refer to the risk assessment

• Refer to the Manufacturers instructions and safety advice.

• Ensure the area is well ventilated.

• Ensure the Nortec

ME

system is OFF and isolated from external controls.

• If the unit is already in operation there is low risks, check for correct operation before cleaning

and dismantling.

Note: if there are concerns over condition of unit, drain unit, flush water supply, and disinfect

tank before starting cleaning work.

• Drain system, dismantle unit and scrub tank fully. For complete disinfection remove droplet separa-

tor banks (if applicable) and the evaporative cassettes to allow a full clean (refer to maintenance

section).

• Consider appropriate maintenance requirements at this time including parts replacement i.e.

replacing distribution hoses to ensure that these are also disinfected.

• Re-assemble the Nortec ME system (refer to installation manual).

Step 2 - Mix disinfection solution

• Mix disinfection solution following the manufacturers instructions. Recommended 50ppm Chlorine

solution circulated for 1 hour minimum or appropriate time. NB: For larger or particularly unclean

systems this process may need to be repeated.

• Calculate the total water volume of the system using wet and dry weight values (see rating plate).

Note: Solution loses strength over time and the solution may need to be increased through the

process or the disinfection process may need to be repeated.

Step 3 - Run the unit

• *Note the various control settings in case it is necessary to override them.

• Disable drain cycles or activate conductivity drain cycles to ensure solution will not be drained

unnecessary.

• Switch the control unit to the on and allow the tank to refill.

• Place the unit into a RUN condition (*control settings may need to be overridden, refer to the

configuration section of this manual).

• Check for correct operation and evaporative cassettes are full saturated.

Advertising