32 Operating the Nortec ME control software

Hours of Operation: Operating hours since initial commissioning of the

system.

Next ME Service: Remaining time until next maintenance of the system

must be performed.

Next UV Bulb: Remaining time until the UV bulb of the optional UV device

must be replaced.

Next PureFlo: Remaining time until the cartridge of the PureFlo Ag+ op-

tion must be replaced.

Maintenance

Evaporator Conditions
The content of the “Evaporator Conditions” information section depends on the set dilution mode.

Dilution mode set to “

Fill Cycle”:

Dillution Fill cycle: Actual set fill cycles for periodical tank draining de-

pending on the fill cycles.

Drain Interval: Actual set tank drain interval time.

Dilution mode set to “

Dilution µS Limit”:

Conductivity: Actual conductivity of the water in the tank in µS (µS/cm).

Water Temperature: Actual temperature of the water in the tank in °C

or °F.

Dillution µS Limit: Actual set conductivity limit value if exceeded a dilution

cycle is triggered.

Drain Interval: Actual set tank drain interval time.

Dilution mode set to “

Dilution H2O Temp”:

Water Temperature: Actual temperature of the water in the tank in °C

or °F.

Dilution H2O Temp: Actual set temperature limit value Actual temperature

of the water in the tank in °C or °F if exceeded a dilution cycle is triggered.

Drain Interval: Actual set tank drain interval time.

Dilution mode set to “

Dilution Interval”:

Dillution Interval: Actual set dilution interval time, for periodic dilution of

the water in the tank.

Drain Interval: Actual set tank drain interval time.