Submenu – Nortec ME Control User Manual

Page 48

Advertising
background image

48 Operating the Nortec ME control software

UV Lamp: With this function you can switch on and off the optional UV

Lamp.

Dosing Pump: With this function you can switch on and off the dosing

pump of the optional system for enhancing polyester media water absorb-

tion.

Control

Control Select: With this function you switch the humidity or demand

control signal between voltage and current signal.

Temp. Select: With this function you switch the temperature control signal

between voltage and current signal.

Hygiene & Safety

5.5.2.3 Relay diagnostic functions – “Relay Diagnostics” submenu

The following diagnostic functions are available after accessing the “Relay Diagnostics” submenu.

General

Running: with this function you can activate (“On”) and deactivate (“Off”)

the relay “Running” on the remote operating and fault indication board,

which indicates that the unit is humidifying/cooling.

Service: with this function you can activate (“On”) and deactivate (“Off”)

the relay “Service” on the remote operating and fault indication board,

which indicates that a service is due.

Fault: with this function you can activate (“On”) and deactivate (“Off”) the

relay “Fault” on the remote operating and fault indication board, which

indicates that a fault is present.

Advertising