Fault elimination

Code

Message

Information

Warning

Fault

Possible causes

Remedy

–––

E86

Driver Incom-

patible

Version of driver board doesn't match, Nortec ME Control automatically stopped

operation. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.

Check fuses on driver board and replace.

Short circuit in control panel.

Check control panel.

Switched power supply unit defective.

Check/replace switched power supply

unit.

–––

E87

Local 24V Supply Local 24V supply out of valid range, Nortec ME Control automatically stopped

operation. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.

Check fuses on driver board and replace.

Short circuit in control panel.

Check control panel.

Switched power supply unit defective.

Check/replace switched power supply

unit.

–––

E88

Local 5V Supply Local 5V supply out of valid range, Nortec ME Control automatically stopped opera-

tion. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.

Check fuses on driver board and replace.

Short circuit in control panel.

Check control panel.

Switched power supply unit defective.

Check/replace switched power supply

unit.

–––

E89

Local Ref Supply Local reference supply out of valid range, Nortec ME Control automatically stopped

operation. The fault message must be reset after elimination of malfunction.
Driver Board defective.

Replace driver board.

–––

E96

Peri. 5V Supply

Peripheral 5V supply out of valid range, Nortec ME Control automatically stopped

operation. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.

Check fuses on driver board and replace.

Short circuit in control panel.

Check control panel.

Switched power supply unit defective.

Check/replace switched power supply

unit.

–––

E100

IO Inlet

The smart output driver detected short circuit or open load on the output of the

inlet valve.
Inlet valve defective.

Replace inlet valve.

Distribution board defective.

Replace distribution board.

Inlet valve not connected.

Correctly connect inlet valve

E103

to

E109

IO Stage x

(e.g. IO Stage 1)

The smart output driver detected short circuit or open load on the output of the

corresponding stage pump.
Corresponding stage pump defective.

Replace corresponding stage pump.

Distribution board defective.

Replace distribution board.

Corresponding stage pump not connect-

ed.

Correctly connect corresponding stage

pump.

E110

IO Drain

The smart output driver detected short circuit or open load on the output of the

drain valve.
Drain valve defective.

Replace corresponding drain valve.

Distribution board defective.

Replace distribution board.

Drain valve not connected.

Correctly connect drain valve.

E111

IO Drain Pump

The smart output driver detected short circuit or open load on the output of the

drain pump.
Drain pump defective.

Replace drain pump.

Distribution board defective.

Replace distribution board.

Drain pump not connected.

Correctly connect drain pump.