Maintenance

Step 4 - Add disinfection solution

• Add the solution to the water sump tray and allow to flow through the evaporative cassettes.

• Measure the strength of the disinfection solution and check it is the correct strength in accord-

ance with manufacturers guidelines.

• Note the strengths of the disinfection solution at 15 minute intervals and record on a record ap-

propriately.

• Adjust solution strength as required.

Step 5 - Circulate disinfection solution

• Check all surfaces are wetted for desired time and correct solution.

Step 6 - Neutralise the disinfection solution – if required based on chemical used

WARNING!

If a neutralising solution is required, always ensure that the neutralising solution is used in accord-

ance with the manufacturer’s guidance. Failure to follow the manufacturer’s guidance with regard

to neutralising the disinfection chemical may present a risk to health.

• Mix neutralising agent as manufacturers instructions.

• Allow the neutralising agent to disperse over the matrix and circulate in the sump tray.

• Drain and measure the strength as per MSDS until the disinfection solution is down to desired

strength.

Step 7 - Drain the unit into foul drain

• Turn Off any fill cycle.

• Drain unit until empty into appropriate drain (depending on Risk Assessment) and rinse the tank

if necessary.

• Fill and drain unit including flushing over the evaporative cassettes and test to ensure that the

chemical is removed to the appropriate level.

• Wipe tank clean.

• *Where required, reset to original setting and put unit back into operation. Test for correct opera-

tion as per commissioning section of the manufacturers manual.

• Check for and complete maintenance requirements as per manufacturers instructions.

• Add DISIFIN XL chemical to the tank.

• Always leave work area clean, dry and tidy.

Step 8 - Re-start the Nortec

ME

system

• Refer to the commissioning section of this manual.

If in doubt always contact your Nortec distributor.