Installation & wiring, Digital room sensor & wall mounted space co, Sensor – Orion System VCM-X Modular E-BUS User Manual

Page 12: Vcm-x modular e-bus controller technical guide 12, Digital room sensor, Wall mounted space co, Zone, Sensor wiring, Sensor for applications requiring both a room co, Sensor is used to monitor co

Advertising
background image

Zone

Zone

INSTALLATION & WIRING

VCM-X Modular E-BUS Controller Technical Guide

12

Digital Room Sensor & Wall Mounted Space CO

2

Sensor

Digital Room Sensor

The OE217-00 Digital Room Sensor is used to sense Space Temperature
and the OE217-01 Digital Room Sensor is used to sense Space Tempera-
ture and Space Humidity. The Sensor connects to the VCM-X E-BUS
Controller with the TSDRSC modular cable. It can be daisy-chained
with the OE256-01 CO

2

Sensor for applications requiring both a room

CO

2

sensor and room temperature sensor. It should be mounted at ap-

proximately 5 Ft. above the fl oor on the wall in an area that does not have
drafts or is exposed to direct sunlight. See Figure 6 for wiring details.

I2C DIGITAL

SENSOR

I2C

EXPANSION

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

WattMaster Label

#LB102033-01

AI1

I1

SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Digital Room Sensor

CO Sensor

2

TSDRSC Cable

TSDRSC Cable

Display

Override

OVERRIDE

ALARM

Note: When a Digital Room Sensor Is
Used In Combination With The

The

r Always

Connects To The VCM-X E-BUS
Controller First Using a TSDRSC Cable
Of The

Length. The Digital

Room Sensor Then Connects To The CO
Sensor With Another TSDRSC Cable.

CO

Sensor,

CO Senso

Required

Mount Sensor(s) At Least 5 Feet Above
Floor. See The

For Further Wiring

2

2

2

E-BUS C

Sensor

Technical Guide

O

2

EMERGENCY SHUTDOWN

VCM-X E-BUS

Controller

I2C DIGITAL

SENSOR

I2C

EXPANSION

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

WattMaster Label

#LB102033-01

AI1

I1

SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

VCM-X E-BUS

Controller

Digital Room Sensor

Display

Override

OVERRIDE

ALARM

TSDRSC Cable

Note: When Only The

Connects Directly To The VCM-X E-

BUS Controller Using A

Of The

Appropriate Length.

Digital Room Sensor

Is Used, It

TSDRSC Cable

The Maximum Length Allowed

Is 160 Feet. See For Connection When
The Space CO Sensor Is Also Used.

Figure 7

2

EMERGENCY SHUTDOWN

Figure 6: OE217-00/01 – Digital Room Sensor Wiring

Figure 7: OE256-01 – Wall Mounted Space CO

2

Sensor Wiring

Wall Mounted Space CO

2

Sensor

The OE256-01 Wall Mounted Space CO

2

Sensor is used to monitor CO

2

levels in the space served by the HVAC unit. The CO

2

Sensor connects to

the VCM-X E-BUS Controller with the TSDRSC modular cable. It can
be daisy-chained with the Digital Room Sensor ( OE217) for applications
requiring both a room CO

2

sensor and room temperature sensor. It should

be mounted at approximately 5 Ft. above the fl oor on the wall in an area
that does not have drafts or is exposed to direct sunlight. See Figure 7
for wiring details and installation notes. A Duct Mounted

CO

2

Sensor

can be used if desired instead of the Wall Mounted Space CO

2

Sensor.

See Figure 8 for Duct Mounted CO

2

Sensor wiring details.

Advertising
This manual is related to the following products: