Additional applications, Aaon, Tulsa full digital module overview and wiring – Orion System VCM-X Modular E-BUS User Manual

Page 42: Tulsa full digital module

Advertising
background image

ADDITIONAL APPLICATIONS

VCM-X Modular E-BUS Controller Technical Guide

42

AAON

®

Tulsa Full Digital Module

The Full Digital Module ( OE370-23-FD-A) is a device that enables and
modulates up to four digital compressors on HVAC Units controlled by
the VCM-X Modular E-BUS Controller ( OE332-23E-VCMX-MOD-
A). The Full Digital Module will control the digital compressors to
satisfy the cooling, dehumidifi cation, and heat pump requirements of
the VCM-X Modular E-BUS Controller.

The Full Digital Module connects to the VCM-X Modular E-BUS
Controller. This allows the Full Digital Module to receive setpoints and
monitor the Supply Air Temperature from the VCM-X Modular E-BUS
Controller.

See Figure 37 below for wiring diagram.

Figure 37: AAON Tulsa’s Full Digital Module Wiring Diagram

AAON

®

Tulsa Full Digital Module Overview and Wiring

The Full Digital Module requires a 24 VAC power connection with an
appropriate VA rating.

NOTE: The Compressor Relays on the Full Digital Module
are used rather than the relay outputs on the VCM-X Modular
E-BUS Controller.

NOTE: For complete information, including the sequence of
operation, refer to the Full Digital Module Technical Guide.

SHLD

SHLD

SHLD

OUT

OUT

OUT

COM

COM

COM

EXC

EXC

EXC

P4

P4

P4

BK

BK

BK

RD

RD

RD

WH

WH

WH

P2

P2

P2

P1

P1

P1

P3

P3

P3

P5

P5

P5

C1

C1

C1

C2

C2

C2

P6

P6

P6

SHLD

OUT

COM

EXC

P4

BK

RD

WH

P2

P1

P3

P5

AO1

SIG 1

SIG 2

SIG 3

SIG 4

AO2

GND

GND

GND

GND

C1

C2

P6

+5V

SIG 2

GND

OPTI

O

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

OE370-23-FD-A

Full Digital Module

Copeland Digital

Compressor Controller B1

Copeland Digital

Compressor Controller A2

Copeland Digital

Compressor Controller A1

Copeland Digital

Compressor Controller B2

This Dip

Switch Is Not

Used For This

Application

This Dip

Switch Is Not

Used For This

Application

PWR

Connect To VCM-X

Modular E-BUS Controller

(See

for details.)

Figure 33

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result in
damage to the boards.

HSSC Cable

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER

ALL RELAY OUTPUTS

ARE

COMPRESSOR A2 ENABLE

COMPRESSOR A1 ENABLE

R1

R4

R3

R2

COMPRESSOR B1 ENABLE
COMPRESSOR B2 ENABLE

ONLY.

1 AMP MAXIMUM LOAD.

HVAC UNIT CONNECTIONS