Installation & wiring, Economizer damper actuator wiring, Vcm-x modular e-bus controller technical guide – Orion System VCM-X Modular E-BUS User Manual

Page 17: Economizer damper actuator

Advertising
background image

VCM-X Modular E-BUS Controller Technical Guide

INSTALLATION & WIRING

17

Figure 13: Economizer Damper Actuator Wiring

24 VAC Power Source

Sized For Actuator VA Load

24 V

A

C

GND

2-10 VDC

Output

Economizer Damper Actuator

(Belimo Actuator Shown)

Y1 3

+ 2

COM - 1

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturer Wiring

Instructions

VCM-X E-BUS Controller

GND

AO1

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Economizer Feedback 5

NOTE: For Economizer

Actuator Feedback Signal,

See

Wiring For The

VCM-X Expansion Module.

AI3

Economizer Damper Actuator

The Economizer Damper Actuator signal voltage output is a 2-10 VDC
output. This signal output is used by the VCM-X E-BUS Controller
to modulate the Economizer Damper Actuator in order to control the
amount of Outdoor Air delivered to the HVAC unit for Free Cooling and/
or Indoor Air Quality requirements. See Figure 13 for detailed wiring.

Warning: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the actuator or VCM-X
E-BUS Controller.

Economizer Damper Actuator Wiring