Installation & wiring, Oat sensor wiring, Vcm-x modular e-bus controller technical guide 16 – Orion System VCM-X Modular E-BUS User Manual

Page 16: Outdoor air temperature sensor, Zone

Advertising
background image

Zone

Zone

INSTALLATION & WIRING

VCM-X Modular E-BUS Controller Technical Guide

16

OAT Sensor Wiring

Outdoor Air

Temperature Sensor

AI4

GND

Make Splice Connections

Inside Sensor Enclosure

As Shown. Seal All Conduit

Fittings With Silicone

Sealant

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

Be Sure Jumper Is Set

For THERM

On AI4 For Outdoor

Air Temperature Sensor

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

VCM-X E-BUS

Controller

For MUA Applications With a
Heat Wheel, Mount Sensor
Downstream of the Heat
Wheel.

Outdoor Air Temperature Sensor

The OE250 Outdoor Air Temperature Sensor must be wired as shown in
Figure 12 below for proper operation of the VCM-X E-BUS Control-
ler. The Outdoor Air Temperature Sensor is a 10K Type III thermistor
sensor. The sensor should be mounted in the upright position as shown
in an area that is protected from the elements and direct sunlight. Be
sure to make the wiring splices inside of the Outdoor Air Temperature
Sensor weather-tight enclosure.

For MUA applications with a Heat Wheel, the Outdoor Air Temperature
Sensor is mounted downstream of the Heat Wheel.

Figure 12: OE250 – Outdoor Air Temperature Sensor Wiring

Caution: Be sure to mount the Outdoor Air Temperature Sensor
in an area that is not exposed to direct sunlight. The shaded area
under the HVAC unit rain hood is normally a good location. Unused
conduit opening(s) must have closure plugs installed and must be
coated with sealing compound to provide a rain-tight seal. Water
can damage the sensor.