Additional applications, Vcm-x modular e-bus controller technical guide, Two condenser head pressure ii module – Orion System VCM-X Modular E-BUS User Manual

Page 39

Advertising
background image

VCM-X Modular E-BUS Controller Technical Guide

ADDITIONAL APPLICATIONS

39

Two Condenser Head Pressure II Module Overview and Wiring

Two Condenser Head Pressure II

Module

The Two Condenser Head Pressure II Module (OE370-23-HP2C2)
monitors four individual head pressure transducers and controls two
Condenser Fans or Water Valves on units with two physically separate
condenser sections. The highest reading of head pressure transducers 1
& 2 controls Condenser Signal A. The highest reading of head pressure
transducers 3 & 4 controls Condenser Signal B. If this is a heat pump
unit, the module is able to detect when the unit is in Heat Pump Heat-
ing mode and will force the condenser signal to 100% until it leaves
this mode.

A pulse width modulation (PWM) signal or 0-10 volt output

signal is used to control the condenser fans.

The Two Condenser Head Pressure II Module connects to the VCM-X
Modular E-BUS Controller ( OE332-23E-VCMX-MOD-A or -C) or the
VCM-X WSHP E-BUS Controller ( OE332-23E-VCMX-WSHP-A or
-C). This allows the Two Condenser Head Pressure II Module to receive
setpoints from the VCM-X Modular E-BUS Controller or VCM-X
WSHP E-BUS Controller. See Figure 35 below for wiring diagram.

The Two Condenser Head Pressure II Module requires a 24 VAC power
connection with an appropriate VA rating.

NOTE: For complete information, including the sequence of
operation, refer to the Two Condenser Head Pressure II Module
Technical Guide
.

Figure 35: Two Condenser Head Pressure II Module Wiring Diagram

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP2C2

Two Condenser Head Pressure II Module

OPTIONS Dip Switch Setting Not Required

When Connected To

VCM-X E-BUS Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

HSSC Cable

Connect To VCM-X E-BUS

Set ADDRESS Dip Switch 1 to ON for

Water Cooled or to OFF for Air Cooled.

Currently showing OFF for Air Cooled.

Set ADDRESS Dip Switch 2 to OFF

on all communicating applications

unless it is intended to be the Second

Head Pressure Module on a system. If

set to ON, it will not communicate.

Currently showing OFF.

Set ADDRESS Dip Switch 3 to ON to

disable Circuit B alarms when only one

Condenser is Used. Currently showing

OFF.

Set ADDRESS Dip Switch 4 to OFF to

make reversing valve "ON to Heat /

OFF to Cool.” Set to ON to make

reversing valve “ON to Cool / OFF to

Heat.” Currently showing OFF.

.

ADDRESS

BIN 1

BIN 2

BIN 3

COM

+24 Volts

Condenser Fan A

ECM Motor

Duty Cycle

Condenser Fan B

ECM Motor

COM

+

Condenser

Signal B

COM

+

Condenser

Signal A

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER B ENABLE

COMM

REVERSING VALVE B ENABLE

REVERSING VALVE A ENABLE

R4

R2

YELLOW

BLUE +24 OUT

+24 Volts

Duty Cycle

YELLOW

BLUE +24 OUT

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL
COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2

Connect To VCM-X

Modular E-BUS Controller or

VCM-X WSHP E-BUS Controller

(See

for details.)

Figure 33

Advertising