Start-up & commissioning, Addressing & powering up, Vcm-x modular e-bus controller technical guide 48 – Orion System VCM-X Modular E-BUS User Manual

Page 48: Before applying power, Controller addressing, Power wiring, Zone, Vcm-x e-bus controller

Advertising
background image

Zone

Zone

START-UP & COMMISSIONING

VCM-X Modular E-BUS Controller Technical Guide

48

Addressing & Powering Up

Before Applying Power

In order to have a trouble free start-up, it is important to follow a few
simple procedures. Before applying power for the fi rst time, it is very
important to correctly address the controller and run through a few
simple checks.

Controller Addressing

All VCM-X E-BUS Controllers are equipped with address switches. If
the VCM-X E-BUS Controller is to operate as a stand-alone system (not
connected to any other HVAC unit or VAV/Zone Controllers), the control-
ler address switch should be set for address 1. When using the Modular
Service Tool or System Manager to program and confi gure the VCM-X
E-BUS Controller, you would enter this address to communicate with
the controller. When the system is to be connected to other HVAC unit
controllers on a communication loop, each controller’s address switch
must be set with a unique address between 1 and 59. When the VCM-X
E-BUS Controller will be used with VAV/Zone Controllers, the VCM-X

E-BUS Controller’s address switch must be set as address 59, no excep-
tions. See Figure 41 below for address switch setting information. For
detailed information regarding communication wiring and connection
for interconnected and networked systems, please see the Orion Systems
Technical Guide—OR-SYS-TGD-XX
.

Power Wiring

One of the most important checks to make before powering up the
system for the fi rst time is to confi rm proper voltage and transformer
sizing for each controller. Each VCM-X E-BUS Controller requires 8
VA of power delivered to it at 24 VAC. Each VCM-X Expansion Mod-
ule requires 10 VA at 24 VAC and each 12-Relay Expansion Module
requires 15 VA at 24 VAC. You may use separate transformers for each
device (preferred) or power several devices from a common transformer.
If several devices are to be powered from a single transformer, correct
polarity must be followed.

Figure 41: VCM-X E-BUS Controller Address Switch Setting

VCM-X E-BUS Controller

16
32

--------

NET

8

4

2

1

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller
Address Switch

This Switch Should Be
In The OFF Position
As Shown

Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch Settings In
Order For Any Changes To Take Effect.

Caution:
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication Loop
Wiring.

ADDRESS

ADD

ADD

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop And Be Between 1 and 59

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label

#LB102073-01-A

Rev.: 1A

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

Advertising