VCM-X Modular E-BUS Controller Technical Guide

INSTALLATION & WIRING

19

VCM-X Expansion Module Input Wiring

Figure 16: OE333-23-EM – VCM-X Expansion Module Input Wiring

VCM-X Expansion Module

Three different Expansion Modules are available for use with the VCM-
X E-BUS Controller to provide additional inputs and outputs beyond
those found on the VCM-X E-BUS Controller.

The VCM-X Expansion Module ( OE333-23-EM) provides 8 Binary
Inputs, 4 Analog Inputs, 4 Relay Outputs, and 5 Analog Outputs. See
Figures 16 below and 17, page 20 for complete wiring details.

Remote Forced Heating - N.O. Contact

Remote Forced Cooling - N.O. Contact

Hood On - N.O. Contact

Dirty Filter - N.O. Contact

Proof Of Flow - N.O. Contact

Remote Forced Occupied - N.O. Contact

VOUT (0-5V)

0-5V

GND

GND

VIN

VAC OR DC

+

-

LOW

HIGH

COM

OUT

EXC

+

+

Emergency Shutdown - N.C. Contact

Remote Forced Dehumidification
N.O. Contact

AI2

B 7

I

B 6

I

B 5

I

B 3

I

B 4

I

B 1

I

B 2

I

Plastic Tubing To Building
Pressure Sensing Locations

Modular Cable

Connect To VCM-X E-BUS

Controller

Modular Cable

Connect To Next Expansion Board

(When Used)

24 VAC

GND

Building Pressure

Transducer

Outdoor Air

Humidity Sensor

Indoor Air

Humidity Sensor

10 VA Minimum Power

Required For

VCM-X Expansion Module

Connect PR OUT To AI5 &

GND To GND On VCM-X

Controller When Either Suction

Pressure Transducer Is Used

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Modules must be wired in such a way that the expansion
modules and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.

Copeland Digital

Compressor Controller

P4

RD

WH

BK

P3

P2

P1

SHLD

EXC

OUT

COM

P5

P6

C1

C2

Suction Pressure

Transducer

BK

RD

WH

Suction Pressure Transducer

Operating Parameters.

Note:
1.) If Unit Has Dehumidification Option And Copeland Digital
Compressor Is Used, Wire Suction Pressure Transducer To
Copeland Controller As Shown.

2.) The Modulating Cooling Output Voltage Must Be
Configured For 1.5 - 5 VDC Operation When You Are
Setting Up The VCM-X Controller

1.) If Unit Has Dehumidification Option
And Copeland Digital Compressor

, Wire Suction Pressure

Transducer Directly To VCM-X
Expansion Module As Shown.

Note:

Is Not

Used

VCM-X Expansion Module

AI1

AI3

AI4

GND

GND

BI8

PR OUT

GND

+V

SIG

GND

Economizer Damper Actuator

(Belimo Actuator Shown)

Y1 3

+ 2

COM - 1

Economizer Feedback 5

See Economizer
Actuator Wiring

For VCM-X

Controller

AO1

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

AO1 = BUILDING PRESSURE CONTROL VFD OR

DAMPER ACTUATOR (0-10 OR 2-10 VDC)

= MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING/DIGITAL SCROLL

SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= RETURN AIR DAMPER ACTUATOR

(0-10 VDC)

= RETURN AIR BYPASS DAMPER ACTUATOR

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

BI1 = HOOD ON - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

WattMaster Label

#LB102034-01

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)

AI2

AI3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

+V

SIG

GND

PR OUT

GND

SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR

TO VCM-X INPUT
TERMINALS AI5 & GND

OE333-23-EM-A VCM-X EXPANSION MODULE

VCM

WA

RN

IN

G

OB

SE

RV

E

POLAR

IT

Y

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

AO1 = BUILDING PRESSURE CONTROL VFD OR

DAMPER ACTUATOR (0-10 OR 2-10 VDC)

= MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING/DIGITAL SCROLL

SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= RETURN AIR DAMPER ACTUATOR

(0-10 VDC)

= RETURN AIR BYPASS DAMPER ACTUATOR

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

WattMaster Label

#LB102034-01-A

Rev.: 1K

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

+V

SIG

GND

PR OUT

GND

SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR

TO VCM-X INPUT
TERMINALS AI5 & GND

BI1 = EMERGENCY SHUTDOWN - N.C. INPUT

= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= HOOD ON - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

www.aaon.com

www.orioncontrols.com

VCM-X Expansion Module

Orion No.:OE333-23-EM

AAON No.:

R69190

AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)

AI2

A3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= ECONOMIZER FEEDBACK
= BUILDING STATIC PRESSURE (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

I

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

AO1 = BUILDING PRESSURE CONTROL VFD OR

DAMPER ACTUATOR (0-10 OR 2-10 VDC)

= MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING/DIGITAL SCROLL

SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= RETURN AIR DAMPER ACTUATOR

(0-10 VDC)

= RETURN AIR BYPASS DAMPER ACTUATOR

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

24 VAC POWER
ONLY

WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

WattMaster Label

#LB102034-01-A

Rev.: 1L

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

+V

SIG

GND

PR OUT

GND

SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR

TO VCM-X INPUT
TERMINALS AI5 & GND

BI1 = EMERGENCY SHUTDOWN - N.C. INPUT

= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= HOOD ON - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

www.aaon.com

www.orioncontrols.com

VCM-X Expansion Module

Orion No.:OE333-23-EM

AAON No.:

R69190

AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)

AI2

A3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= ECONOMIZER FEEDBACK
= BUILDING STATIC PRESSURE (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

I

The VCM-X Expansion Module can be used in conjunction with the
12-Relay Expansion Module (OE358-23-12R-A).

The 4 Binary Input Expansion Module (OE356-01-BI) can be used in
place of the VCM-X Expansion Module if your system does not need
any other inputs or outputs.