VCM-X Modular E-BUS Controller Technical Guide

INSTALLATION & WIRING

35

Air Flow Monitoring Station Installation and Wiring

Figure 32: OE365-15-EBA - EBTRON

®

GTC116 Series, GreenTrol

TM

GA-200-N Series, and Paragon

MicroTrans

EQ

Series Air Flow Measurement Digital Transmitter Wiring

COMM

COMM

NET-

NET-

NET+

NET+

Airflow Measurement

Digital Transmitter Terminals

For Outdoor Air CFM

(Set Address Switch To 9)

Airflow Measurement

Digital Transmitter Terminals

For Return Air CFM

(Set Address Switch To 10)

Airflow Measurement

Digital Transmitter Terminals

For Supply Air CFM

(Set Address Switch To 11)

COMM

NET-

NET+

VCM-X E-BUS Controller

OE365-15-EBA

E-BUS Adapter Board

HSSC Cable Connect To

VCM-X E-BUS Port

I2C DIGITAL

SENSOR

I2C

EXPANSION

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

WattMaster Label

#LB102033-01

AI1 AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

EMERGENCY SHUTDOWN

AI1 SET

AI1

THERM

THERM

4-20mA
0-10V

0-5V

ANALOG INPU

JUMPER

SETTINGS

HSSC Cable Connect To

VCM-X E-BUS Port

Connect To

VCM-X E-BUS Port

NOTE: Set Airflow Monitoring
Station’s Baud Rate To 9600
In Order To Communicate
With The VCM-X.

Air Flow Monitoring Station

Installation and Wiring

The OE365-15-EBA E-BUS Adapter Board is used to connect selected
Air Flow Monitoring Stations to the VCM-X Controller. Currently, there
are up to three Air Flow Monitoring Station options that are supported
in our standard software.

• EBTRON

®

– GTC-116 Series Air Flow Monitoring Station*

GreenTrol™ Automation – GA-200-N Module used with

any GF Series Air Flow Monitoring Station

Paragon MicroTrans

EQ

series Air Flow Monitoring Station

The wiring for all three Air Flow Monitoring Stations are the same and
are shown in Figure 32.

NOTE: The Airfl ow Station’s baud rate needs to be set to 9600
in order to communicate with the VCM-X Controller.

*NOTE: When confi guring the GTC-116 Series, be sure to set
the Parity to “NO PARITY, 1 STOP BIT.”

NOTE: Up to 3 EBTRON

®

, GreenTrol

TM

, or Paragon Airfl ow

Measurement Digital Transmitters can be attached to each Adapter
Board.

NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) may be required.