OVERVIEW

5

Features

The VCM-X E-BUS series of controllers now consists of the VCM-X
Modular E-BUS Controller and the VCM-X WSHP (Water Source Heat
Pump) E-BUS Controller. The VCM-X Modular E-BUS Controller has
replaced the standard VCM-X Controller. The E-BUS versions of these
controllers now allow the various E-BUS modules to connect directly
to the VCM-X E-BUS Controllers.

Each of these types of controllers has a version applicable to AAON

®

Tulsa units and a different version applicable to AAON

®

Coil units. The

following is a breakdown of the different versions:

•

AAON

®

Tulsa VCM-X Modular E-BUS Controller

(OE332-23E-VCMX-MOD-A) uses software SS1030

•

AAON

®

Tulsa VCM-X WSHP E-BUS Controller

(OE332-23E-VCMX-WSHP-A) uses software SS1032

•

AAON

®

Coil VCM-X Modular E-BUS Controller

(OE332-23E-VCMX-MOD-C) uses software SS1034

•

AAON

®

Coil VCM-X WSHP E-BUS Controller

(OE332-23E-VCMX-WSHP-C) uses software SS1033

These controllers are designed with 7 analog inputs, 2 analog outputs,
and 5 relay outputs. Each VCM-X E-BUS Controller’s input and out-
put capabilities can be expanded with the VCM-X Expansion Module
(OE333-23-EM), the 12 Relay Expansion Module (OE358-23-12R),
and the 4 Binary Input Expansion Module (OE356-01-BI) by means of
a modular cable. Each VCM-X E-BUS Controller can be confi gured for
control of VAV Units (with or without VAV/Zone Controllers), Constant
Volume Units, and Make-Up Air Units. Features include the following:

•

Up to a Combined Total of 20 Stages of Heating & Cooling

•

Modulating Cooling Output ( Copeland Digital

Scroll™ Compressor or Chilled Water Valve Control)

•

Modulating Heating Output ( Hot Water Valve,

Steam Valve, SCR Electric Heat Control)

•

Full Integration with the AAON

®

MODGAS Modulating

Natural Gas Controller

•

Full Integration with the AAON

®

MHGRV Modulating

Hot Gas Reheat Controller

•

Confi gurable for Heat Pump Applications

•

Advanced Dehumidifi cation Capabilities

•

Air Flow Monitoring of Outdoor Air, Supply Air,

and Return Air Streams

•

Air Flow Control of Outdoor Air Damper

•

Single Zone VAV Control

•

Primary/Secondary Heating Control

•

Adaptive Supply Air Reset

•

Micro Channel Condenser Control

Features and Applications

•

Selectable Control Sensor

•

Fan Proving Interlock

•

Dirty Filter Alarm

•

Emergency Shutdown Input (Smoke Detector/Firestat or

other Shutdown Conditions)

•

Drybulb/Wetbulb Control of Economizer Operation

•

Building Pressure Control

•

Remote Override Capabilities

•

IAQ Economizer Reset

•

Title 24 Economizer Certifi ed

•

7-Day, 2-Event-per-Day Scheduling

•

14 Holiday Event Scheduling

•

Optimal Start Scheduling

•

Trend Logging Capability

•

Static Pressure Control for Filter Loading Applications

•

Accepts Remote HVAC Mode Selection Via Contact

Closure On VCM-X Expansion Module

•

Confi gurable for AAON

®

PAC and DPAC Applications

•

Heat Wheel - On/Off Control

•

Confi gurable for R22 and R410-A refrigerant

•

Head Pressure Control (VCM-X Modular E-BUS and

VCM-X

WSHP

E-BUS)

•

Full Digital and Dual Digital Control (VCM-X Modular

E-BUS)

•

Water Source Heat Pump Monitoring (VCM-X WSHP

E-BUS)

Most common HVAC unit control applications can be confi gured using
only the VCM-X E-BUS Controller. If the application requires more in-
puts and/or outputs, optional expansion modules are available to provide
for additional analog, binary, or digital inputs and outputs as required.

The available expansion module confi gurations allow for 4 or 8 ad-
ditional binary inputs, 4 additional analog inputs, 5 additional analog
outputs, and up to 16 additional binary (relay) outputs. The various
expansion modules plug into the VCM-X E-BUS Controller by means
of a modular cable.