Overview, Features and applications – Orion System VCM-X Modular E-BUS User Manual

Page 5

Advertising
background image

VCM-X Modular E-BUS Controller Technical Guide

OVERVIEW

5

Features

The VCM-X E-BUS series of controllers now consists of the VCM-X
Modular E-BUS Controller and the VCM-X WSHP (Water Source Heat
Pump) E-BUS Controller. The VCM-X Modular E-BUS Controller has
replaced the standard VCM-X Controller. The E-BUS versions of these
controllers now allow the various E-BUS modules to connect directly
to the VCM-X E-BUS Controllers.

Each of these types of controllers has a version applicable to AAON

®

Tulsa units and a different version applicable to AAON

®

Coil units. The

following is a breakdown of the different versions:

AAON

®

Tulsa VCM-X Modular E-BUS Controller

(OE332-23E-VCMX-MOD-A) uses software SS1030

AAON

®

Tulsa VCM-X WSHP E-BUS Controller

(OE332-23E-VCMX-WSHP-A) uses software SS1032

AAON

®

Coil VCM-X Modular E-BUS Controller

(OE332-23E-VCMX-MOD-C) uses software SS1034

AAON

®

Coil VCM-X WSHP E-BUS Controller

(OE332-23E-VCMX-WSHP-C) uses software SS1033

These controllers are designed with 7 analog inputs, 2 analog outputs,
and 5 relay outputs. Each VCM-X E-BUS Controller’s input and out-
put capabilities can be expanded with the VCM-X Expansion Module
(OE333-23-EM), the 12 Relay Expansion Module (OE358-23-12R),
and the 4 Binary Input Expansion Module (OE356-01-BI) by means of
a modular cable. Each VCM-X E-BUS Controller can be confi gured for
control of VAV Units (with or without VAV/Zone Controllers), Constant
Volume Units, and Make-Up Air Units. Features include the following:

Up to a Combined Total of 20 Stages of Heating & Cooling

Modulating Cooling Output ( Copeland Digital

Scroll™ Compressor or Chilled Water Valve Control)

Modulating Heating Output ( Hot Water Valve,

Steam Valve, SCR Electric Heat Control)

Full Integration with the AAON

®

MODGAS Modulating

Natural Gas Controller

Full Integration with the AAON

®

MHGRV Modulating

Hot Gas Reheat Controller

Confi gurable for Heat Pump Applications

Advanced Dehumidifi cation Capabilities

Air Flow Monitoring of Outdoor Air, Supply Air,

and Return Air Streams

Air Flow Control of Outdoor Air Damper

Single Zone VAV Control

Primary/Secondary Heating Control

Adaptive Supply Air Reset

Micro Channel Condenser Control

Features and Applications

Selectable Control Sensor

Fan Proving Interlock

Dirty Filter Alarm

Emergency Shutdown Input (Smoke Detector/Firestat or

other Shutdown Conditions)

Drybulb/Wetbulb Control of Economizer Operation

Building Pressure Control

Remote Override Capabilities

IAQ Economizer Reset

Title 24 Economizer Certifi ed

7-Day, 2-Event-per-Day Scheduling

14 Holiday Event Scheduling

Optimal Start Scheduling

Trend Logging Capability

Static Pressure Control for Filter Loading Applications

Accepts Remote HVAC Mode Selection Via Contact

Closure On VCM-X Expansion Module

Confi gurable for AAON

®

PAC and DPAC Applications

Heat Wheel - On/Off Control

Confi gurable for R22 and R410-A refrigerant

Head Pressure Control (VCM-X Modular E-BUS and

VCM-X

WSHP

E-BUS)

Full Digital and Dual Digital Control (VCM-X Modular

E-BUS)

Water Source Heat Pump Monitoring (VCM-X WSHP

E-BUS)

Most common HVAC unit control applications can be confi gured using
only the VCM-X E-BUS Controller. If the application requires more in-
puts and/or outputs, optional expansion modules are available to provide
for additional analog, binary, or digital inputs and outputs as required.

The available expansion module confi gurations allow for 4 or 8 ad-
ditional binary inputs, 4 additional analog inputs, 5 additional analog
outputs, and up to 16 additional binary (relay) outputs. The various
expansion modules plug into the VCM-X E-BUS Controller by means
of a modular cable.