VCM-X Modular E-BUS Controller Technical Guide

ADDITIONAL APPLICATIONS

37

OE370-23-XX or OE334-23-XX

Typical E-BUS Module

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC. Failure to
observe polarity could result in damage
to the boards.

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

HSSC Cable

Connect To VCM-X

E-BUS Controller

VCM-X E-BUS Controller to E-BUS Module Wiring

Figure 33, cont.: VCM-X E-BUS Controller to E-BUS Module Wiring Diagram

NOTE: Contact Factory for the correct HSSC cable length
for your application. Cables are available in ½ meter, 3 meter,
100 foot, and 150 foot lengths.

WARNING: Be sure all controllers and modules are

powered down before connecting or

disconnecting HSSC cables.