Installation & wiring, Vcm-x modular e-bus controller technical guide, Condenser signal 4 – Orion System VCM-X Modular E-BUS User Manual

Page 41: Condenser signal 3, Condenser fan 3 ecm motor, Condenser fan 4 ecm motor

Advertising
background image

VCM-X Modular E-BUS Controller Technical Guide

INSTALLATION & WIRING

41

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers 3 - 4

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP2C2

Two Condenser Head Pressure II Module

OPTIONS Dip Switch Setting Not

Required When Connected To

VCM-X Controller.

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

Set ADDRESS Dip Switch 1 to ON

for Water Cooled or to OFF for Air

Cooled. Currently showing OFF for

Air Cooled.

Set ADDRESS Dip Switch 2 to ON

on 2nd Head Pressure Module.

Set ADDRESS Dip Switch 3 to ON to

disable Circuit B alarms when only

one Condenser is used. Currently

showing OFF.

Set ADDRESS Dip Switch 4 to OFF

to make reversing valve "ON to Heat

/ OFF to Cool.” Set to ON to make

reversing valve “ON to Cool / OFF to

Heat.” Currently showing OFF.

BIN 1

BIN 2

BIN 3

COM

COM

+

Condenser

Signal 4

COM

+

Condenser

Signal 3

CONDENSER 3 ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER 4 ENABLE

COMM

REVERSING VALVE 4 ENABLE

REVERSING VALVE 3 ENABLE

R4

R2

+24 Volts

Condenser Fan 3

ECM Motor

Duty Cycle

Condenser Fan 4

ECM Motor

YELLOW

BLUE +24 OUT

+24 Volts

Duty Cycle

YELLOW

BLUE +24 OUT

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL
COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2

Figure 36, cont.: Four Compressor Micro Channel Condenser Wiring for the HP2C2

Four Compressor Micro Channel Condenser Wiring for the HP2C2

Advertising
This manual is related to the following products: