Additional applications, Aaon, Coil dual digital module overview and wiring – Orion System VCM-X Modular E-BUS User Manual

Page 43: Vcm-x modular e-bus controller technical guide, Coil dual digital module

Advertising
background image

VCM-X Modular E-BUS Controller Technical Guide

ADDITIONAL APPLICATIONS

43

AAON

®

Coil Dual Digital Module Overview and Wiring

Figure 38: AAON Coil Dual Digital Module Wiring Diagram

SHLD

OUT

COM

EXC

P4

BK

RD

WH

P2

P1

P3

P5

C1

C2

P6

SHLD

OUT

COM

EXC

P4

BK

RD

WH

P2

P1

P3

P5

A 1

O

SIG 1

SIG 3

GND

GND

GND

C1

C2

P6

+5V

SIG 2

GND

OPTI

O

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

Connect To VCM-X

Modular E-BUS Controller

(See

for details.)

Figure 33

OE370-23-DD-C

Dual Digital Module

Copeland Digital

Compressor Controller A1

Copeland Digital

Compressor Controller B1

This Dip

Switch Is Not

Used For This

Application

This Dip

Switch Is

Not Used

For This

Application

OE370-23-FD FULL DIGITAL COMPRESSOR MODULE

www.orioncontrols.com

+5V

SIG 2

GND

+5V

SIG 1

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

BIN 1

BIN 2

COM

AO1

AO2

GND

NOT USED

NOT USED

NOT USED

NOT USED

COMPRESSOR #2

COMPRESSOR #1

COPELAND CNTRLR P6

COPELAND CNTRLR P6

COPELAND CNTRLR P5

COPELAND CNTRLR P5

NOT USED

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. #2 ENABLE

COMP. #1 ENABLE

COMP. #1 CNTRLR C2
COMP. #2 CNTRLR C2

COMP. #1 & #2 CNTRLR C1

R1

R2

R3

R4

RC

NOT USED

NOT USED

RELAY COMMON

E-BUS

Connector

E-BUS

Connector

WattMaster Label

#LB102056

+2

4

VA

C

GN

D

PWR

A 2

O

NOTE:

NORMALLY

OPEN AND RATED FOR 24 VAC POWER ONLY

ALL RELAY OUTPUTS ARE

COMPRESSOR A2 ENABLE

COMPRESSOR A1 ENABLE

R1

R4

R3

R2

COMPRESSOR B1 ENABLE
COMPRESSOR B2 ENABLE

- 1 AMP MAXIMUM LOAD

HVAC UNIT CONNECTIONS

HSSC Cable

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
to observe polarity could result in
damage to the boards.

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

COMM

AAON

®

Coil Dual Digital Module

The Dual Digital Module ( OE370-23-DD-C) is a device that enables
and modulates two digital compressors on HVAC Units controlled by
the VCM-X Modular E-BUS Controller ( OE332-23E-VCMX-MOD-
C). The Dual Digital Module will control the digital compressors to
satisfy the cooling, dehumidifi cation, and heat pump requirements of
the VCM-X Modular E-BUS Controller.

The Dual Digital Module connects to the VCM-X Modular E-BUS
Controller. This allows the Dual Digital Module to receive setpoints
and monitor the Supply Air Temperature from the VCM-X Modular
E-BUS Controller.

See Figure 38 below for wiring diagram.

The Dual Digital Module requires a 24 VAC power connection with
an appropriate VA rating.

NOTE: The Compressor Relays on the Dual Digital Module
are used rather than the relay outputs on the VCM-X Modular
E-BUS Controller.

NOTE: For complete information, including the sequence of
operation, refer to the Dual Digital Module Technical Guide.

Advertising