ADDITIONAL APPLICATIONS

VCM-X Modular E-BUS Controller Technical Guide

38

One Condenser Head Pressure Module Overview and Wiring

One Condenser Head Pressure Module

The One Condenser Head Pressure Module ( OE370-23-HP1C) monitors
four individual head pressure transducers and controls the Condenser
Fan or Water Valve based on the highest of the four readings.

A pulse

width modulation (PWM) signal or 0-10 volt output signal is used to
control the condenser fan.

The One Condenser Head Pressure Module connects to the VCM-X
Modular E-BUS Controller ( OE332-23E-VCMX-MOD-A) or VCM-X
WSHP E-BUS Controller ( OE332-23E-VCMX-WSHP-A). This allows
the One Condenser Head Pressure Module to receive setpoints from
the VCM-X Modular E-BUS Controller or VCM-X WSHP E-BUS
Controller. See Figure 34 below for wiring diagram.

The One Condenser Head Pressure Module requires a 24 VAC power
connection with an appropriate VA rating.

NOTE: For complete information, including the sequence of
operation, refer to the One Condenser Head Pressure Module
Technical Guide
.

Figure 34: One Condenser Head Pressure Module Wiring Diagram

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

COM

Condenser Fan

ECM Motor

+

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP1C

One Condenser Head Pressure Module

Connect To VCM-X

Modular E-BUS Controller or

VCM-X WSHP E-BUS Controller

(See

for details.)

Figure 33

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

COM

Condenser

Signal

+

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result
In damage to the boards.

HSSC Cable

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

COMM