Audible Alarm

This field Enables and Disables the CSU’s internal buzzer which alerts users of an
alarm condition.

Alarm

Configuration

The Alarm Configuration screen (Figure 4-15) allows reviewing and setting alarm-
related thresholds (minimum acceptable performance levels) for the unit. Alarm
conditions may be reported by alarm relay contacts and/or by an audible alarm. If
an error condition exceeds the preset alarm thresholds, the red Status LED on top
of the front panel, the LOC ALM LED, and the alarm relay are activated.

If the Alarm Reset Timer period elapses with no further errors detected, the alarm
relay and both LEDs clear. If the ACO (Alarm Cut Off) switch is activated while
an alarm condition exists, the Status LED and alarm relay clear. The LOC ALM
LED remains lit until the Alarm Reset Timer period elapses.

To modify the default parameters, highlight the desired statistic, type in the new
value (any number from 0 to 900) and press Enter. If this value is later surpassed,
an alarm indication appears. A field set to 0 causes the CSU not to alarm on that
statistic. Refer to the Installation chapter for more information on manually setting
alarm configurations.

Errored Seconds

A one-second period in which at least one ESF error event occurred.

Severely Errored Seconds

A one-second period in which at least 320 CRC errors or one OOF (out-of-frame)
occurred.

Loss of Signal Seconds

A one-second period in which the T1 received signal is interrupted.

2000 CSU x.xx/x.xx

2000 CSU Date

MM/DD/YY

2000 CSU x.xx/x.xx

(Unit Address: xxx)

Time HH:MM:SS

----------------------------- ALARM CONFIGURATION ------------------------------

Element: [NEAR]

Errored Seconds (ES): ( 45)

Remote Alarm Seconds (RAS): ( 0)

Severely Errored Seconds (SES): ( 5)

AIS Seconds (AISS): ( 0)

Loss of Signal Seconds (LOSS): ( 5)

Out of Frame Seconds (OOFS): ( 5)

Unavailable Seconds (UAS): ( 0)

BPV Seconds (BPVS): ( 0)

DTE LOS/OOF Seconds (LOSS): ( 5)

Alarm Reset Timer (seconds): ( 30)

(GO TO LINE SETTINGS)

Figure 4-15 Alarm Configuration