DCSU 2911 Quick Set-Up

This chapter provides step-by-step procedures for setting up your
DCSU 2911 module. This quick configuration guide makes the
following assumptions:

You are adding the DCSU 2911 and an NCM 2000 module to an
existing installation in a dual-line shelf.

You are putting two T1s on the two equipment (DSX-1) ports of
the DCSU 2911.

ESF/B8ZS T1s

You are using the NCM 2000 controller module in slot 1 of
shelf 1.

Figure 2-1

Example Configuration

NOTE: These procedures may not match your configuration. Use this

chapter as a guide for equipment installation. Chapter 3 provides

details on configuration options.

Installation

Do the following before installing the DCSU 2911:

Install all associated Access System 2000 shelves and power
supplies, as outlined in the

AS2000: The Basics

manual.

Install and test the NCM in slot 1.

Install the DCSU in slot 2 as outlined in the

AS2000: The Basics

manual.

Management

Terminal/PC

Full T1

24 DS0s

NCM 2000

DCSU 2911

DS1 Port

PBX, Router or

DSX-1 Port

Channel Bank

Full T1

24 DS0s

DS1 Port

PBX, Router or

DSX-1 Port

Channel Bank