Chapter 2 - Start-Up Instructions

DCS 500B / DCP 500B Operating Instructions

IV A

2 - 1

General notes

CAUTION: it is absolutely essential that the applicable accident prevention

regulations be observed by the user (in this context, please also

read the chapter entitled "Safety Instructions")!

How this chapter is structured

For better understanding the individual steps of start-up work are distinguished by
a) frames

without

any additional

marking on the left side:

These steps of start-up work must always be performed

(= mandatory start-up work)!

Example:

522 = GERMAN

[Only with the SDCS-CON-2 control board & the CDP 312 panel!]

Activates German texts on the display ...........

b) frames

with

marking on the left side

(„columns“ shaded in grey)

:

These steps of start-up work have to be performed only when the condition stated

(as heading) applies to the selected drive configuration!

After this work has been

completed,

the

mandatory start-up work

has to be continued

.

Example:

Only when connection diagram 1 (Appendix A) is being used!

906 = 12502

Function „EMERGENCY STOP“ de-activated ............

Recommended motor voltages and field voltages

Motor voltage U

A

when the following units are used

DCS 501B / DCP 501B:

U

Amax

= Line voltage * 1.16

(2- quadrant unit)

DCS 502B / DCP 502B:

U

Amax

= Line voltage * 1.05

(4- quadrant unit)

Field voltage U

F

(= max. output voltage) when the following is being used

SDCS-FEX-1:

U

F

= Line voltage * 0.9

If there is a divergence of more than 10 % between the field supply unit's output

voltage and the rated field voltage U

Frated

stated on the motor's rating plate, then the

connecting voltage U

N

should be reduced, using a matching transformer or a series

resistor R

v

:

R

v

= (0.9 * U

N

- U

F

) / I

F

I

F

= Rated field current

(Note: also suitable for fine-balancing the maximum motor voltage)

Field voltage U

F

when the following is being used

SDCS-FEX-2 /
DCF 503 / DCF 504:

U

F

= Line voltage * 0.6 ... 0.8

Field voltage U

F

when the following is being used

DCF 501B / DCF 502B:

U

F

= Line voltage * 0.5 ... 1.1

Maximally possible output voltage U

Amax

using

DCF 501B / DCF 502B:

U

F

= Line voltage * 1.35