background image

Chapter 2 - Start-Up Instructions

DCS 500B / DCP 500B Operating Instructions

IV A

2 - 11

Drive must not turn!

Do not preset an external reference!

1201 = 3

Panel display: ARM. AUTOTUNING

Activate the current controller's auto-tuning function.

Start the next two steps within the next 20 seconds!

Switch ON power.

DANGER: System components now energized!

Start drive.

When the display shows NOT ACTIVATED (action correctly completed),
stop drive; it may happen that the unit runs armature-circuit current since
e.m.f. control is active; n

min

- signal (2201)

value too small.

Switch OFF power!

Read out values of:
407 = ............ 408 = ............ 409 = ............ 410 = ............ 411 = ............

Use values of 409 and 410 from the first auto-tuning routine.
Re-activate the field unit used by entering:
a)

505 = 1

Panel display: DIODE FIELD EXCIT

and install the supply fuses removed before!

or
b)

505 = 2

Panel display: FEX2 OR FEX3

CAUTION! Please don't forget!

11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!

3ADW000055R0401_DCS500B_Operating Instruction_e_d