2.7 Balancing the speed controller, plus fine-balancing the e.m.f. and the
current

controllers

1701 = 11206
Change between POT1 and POT2 activated.
Extremely reduce the ramp-up time, depending on the system conditions:
1708 = 0,1 s
1709 = 0,1 s

Adjusting the potentiometers for speed controller balancing:
During acceleration/ braking, the drive should reach the current limitation, if
necessary increase the value of POT1.
Scaling of 1204 and 1205

20 000 corresponds to 100 % speed.

1204 (POT1) = 10%...20% max. speed
1205
(POT2) = 0
1206
(PERIOD) = Adapt as necessary.

Switch ON power; start drive.

DANGER: System components now energized!

Drive should run at speed values corresponding to POT1 and „0“.

For assessing control quality, the Fig. entitled "Transient response of
controller" (

section 2.6.3) can be used.

For this purpose, the following parameters at the speed controller must be adapted:
2014 = desired response (behaviour) of controller
2018 = desired response (behaviour) of controller

Only when fine-balancing of the e.m.f. controller is wanted!

((Necessary when work as per section 2.6.3. has been performed)

Only when fine-balancing of the current controller is wanted!

For assessing control quality, the Fig. entitled "Transient response of
controller" (

section 2.6.3) can be used.

- If

fine-balancing of the current controller is wanted, the settings for

the software potentiometers can be retained.

The following parameters at the current controller must be adapted:
407 = desired response (behaviour) of controller
408
= desired response (behaviour) of controller

- If

fine-balancing of the e.m.f. controller is wanted, potentiometers'

settings must be adapted:

1204 (POT1) approx. 10 % smaller than speed at field weakening point
1205 (POT2) ca. 10% greater than speed at field weakening point
The following parameters at the e.m.f. controller must be adapted:
1007 = desired response (behaviour) of controller
1008 = desired response (behaviour) of controller.