Chapter 2 - Start-Up Instructions

DCS 500B / DCP 500B Operating Instructions

IV A

2 - 7

Set this only for units of the DCP 500 series!

517 = Rated power converter current

Enter numerical value from rating plate here

518 = 500 V (fixed!); rated power converter voltage

Enter numerical value 500 V here

519 = Temperature monitoring of power section

Enter value as indicated in the table „Technical Data“ here

520 = 4

Size C4 has been selected

Coding for unit type

521 = 1 : Single bridge (2-Q) converter

on rating plate: DCP 501 xxxx

4 : Double bridge (4-Q) converter

on rating plate: DCP 502 xxxx

Coding for power section (bridge) type

507 = Rated line voltage;

Enter:

Rated line voltage U

ratedline

in V * 1.05

Example: U

ratedline

= 400 V; entry for Parameter 507

420

CAUTION: Display of the line voltage feedback value is 5 % too high!

Switching thresholds referenced to the line voltage, how-

ever, are correct!

CAUTION! Please don't forget!

11202 = SAVE MOT1 SET

Save the altered values in the non-volatile memory!

Resetting the warning either by:
briefly setting ("H“ level) binary input X6:6
or
switching the electronics voltage supply OFF and ON again.