Chapter 2 - Start-Up Instructions

IV A

2 - 16

DCS 500B / DCP 500B Operating Instructions

2.6.3 Field weakening control with setting range > 1 : 1.5

CAUTION: Not permitted when Chapter 2.5 was quit with e.m.f. control!

Only when unit is fitted with an SDCS-CON-1 control board!

If the field time constant is known, e.g. from the motor data sheet!

1308 =

leave as it is; if appropriate vary between 1...5.

P-gain of the field current controller
1309 =

Enter value of field time constant, if necessary increase by factor 1...2.

I-gain of the field current controller
If possible, check controller behaviour with oscilloscope or CMT tool
11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!

If the field time constant is not known!

1201 = 7

Panel display: FEXC2/3 MAN. TUNIN

Drive Mode: manual balancing of the field current controller
1204 = 4095
1205 = 1000

Ref. value jumps of field current between 25 % and 100 % with POT1 and POT2

11209 = 3
Change between POT1 and POT2 activated
12516 = 0

Switch ON power.

DANGER: System components now energized!

1308 = Match P-gain to field circuit.
1309 = Match I-gain to field circuit.
Oscillograph field current feedback via D/A output, or if one is to hand, use CMT
tool to depict it via the TRENDING menu and Parameter

11302

.

t

A

B

C

D

E

F

Fig.: Transient response of controller

A: reference value jump

B: undercompensated; reset time and P-gain too small

C:

undercompensated; P-gain too small

D:

normal

E: slightly overcompensated; when a higher dynamic response is required

F: overcompensated; short reset time and a high P-gain