Chapter 2 - Start-Up Instructions

DCS 500B / DCP 500B Operating Instructions

IV A

2 - 13

Only when an encoder (pulse encoder) is being used!

12104 = Content of pulse counter
If the shape of the curve corresponds to the diagram below, this means
the wiring is correct and the pulses will be correctly evaluated [see
also documentation entitled „Technical Data“, Chapter I/O boards].

0

65535

Fig.: Curve shape of the encoder’s pulse counter for sense of rotation "forwards“

Switch OFF power, thus stopping the drive; drive coasts.

2101 = No. of encoder pulses
As specified on the encoder's rating plate
2102 = 3

Panel display: ENCODER A+-, B+-

Encoder is used for speed control.

Switch ON power; start drive.

DANGER: System components now energized!

Drive should run at 10 % of the desired speed;
if possible, check with manual tacho.

Only when the e.m.f. signal is being used as speed feedback!

Drive should run at 10 % of the desired speed;
if possible, check with manual tacho.

Switch OFF power, thus stopping the drive; drive coasts.

CAUTION! Please don't forget!

11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!