Chapter 4 - Signals and Troubleshooting


DCS 500B / DCP 500B Operating Instructions

IV A

4 - 19

Para-

meter

Code

/

bit

Text on LCD of con-

trol panel CDP 31x

Definition / explication of the signal

Remark

6

READ APPL BLOCKS

Load application; if additional function blocks are ac-
tivated and saved via SAVE MOTx SET and modified
afterwards without saving the configuration before
the last modification (the one directly after the last
SAVE action) can be activated

11202

--

----

While the command is executing the value of
BACKUPSTOREMODE will show what is happening
or the reason for error if the command fails

7

ERASE ERROR

Error during erasing of parameter flash

8

ERASING…

Erasing the parameter flash

9

PROGRAM ERROR

Error during programing of parameter flash

10

PROGRAMMING…

Programing the parameter flash

11

WRONG FLASH TYPE

Verification error

12

READING…

Reading the parameter flash

13

READ ERROR

Error during reading of parameter flash

14

reserved

15

VERSION ERROR

Bad type of parameter flash

16

reserved

17

SIZE ERROR

Bad size of parameter flash

11203

-- ---- FEXC_STATUS:

Status of the field exciters 1 and 2

00

(FEXC1_RDY_OPER)

0 = not ready for operation; AC-voltage missing

01

(FEXC1_OK)

0 = self diagnostic failed or power failure in FEX 1

02

(EXC2_RDY_OPER)

0 = not ready for operation; AC-voltage missing

03

(EXC2_OK)

0 = self diagnostic failed or power failure in FEX 2

04

(ACK_FEXC1_ON)

1 = motor 1 field OK

05

(ACK_FEXC2_ON)

1 = motor 2 field OK

06

(FIELD_HEAT_ON)

1 = motor heating function active

07

(FIELD1_REV_ACK

direction of the field 0 = forward, 1 = reverse

08

(ACK_CSC_ON)

1 = on-command accepted by sequence control

09

(ACK_FEXC_ON

1 = motor field OK

10

(FIELD_REF_ON)

1 = field current reference released

11

(FIELD1_CURR_MIN_L)

1 = motor 1 field current above min level

3ADW000055R0401_DCS500B_Operating Instruction_e_d