Iv a, Switch off power, thus stopping the drive, Chapter 2 - start-up instructions – DCS 500 User Manual

Page 30

Advertising
background image

Chapter 2 - Start-Up Instructions

IV A

2 - 18

DCS 500B / DCP 500B Operating Instructions

12522 = decrease so that motor voltage is 90 %.
Flux and thus the field current as well are reduced.
How to proceed:
1. decrease

12522 (in steps of 100 at a time)

2. press

ACT, read off motor voltage

3. press

PAR and correct 12522 if necessary (then continue with 2.)

Read out and note down value of:
11003 = .........

(will later be entered in 1015)

12522 = decrease so that motor voltage is 70%.
Flux and thus the field current as well are reduced.

Proceed as described in (1. / 2. / 3.) above!

Read out and note down value of:
11003 = .........

(will later be entered in 1014)

12522 = decrease so that motor voltage is 40%.
Flux and thus the field current as well are reduced.

Proceed as described in (1. / 2. / 3.) above!

Read out and note down value of:
11003 = .........

(will later be entered in 1013)

12522 = 4095
12516 = 0
Internal reference value equal to zero.

Switch OFF power, thus stopping the drive!

1002 = 12512
1004 = 0
1009 = 10%
1010 = - 99%
As-delivered values (default values) for all 4 parameters restored.
1015 = equal to the 1st value of 11003
1014
= equal to the 2nd value of 11003
1013
= equal to the 3rd value of 11003
Linearization function matched to field circuit.

501 = 90 % of the rated motor voltage.
1012 = 90 % of the value on the motor rating plate.

This measure serves to provide a greater safety margin for the motor voltage
during start-up.

3ADW000055R0401_DCS500B_Operating Instruction_e_d