Chapter 3 - Handling of Control Panel CDP 31x

IV A

3 - 10

DCS 500B / DCP 500B Operating Instructions

3.9 Uploading and Downloading of Parameters (UPLOAD/DOWNLOAD)

CAUTION! The drive must be in standstill condition with given

STOP command (controllers blocked, power section
disconnected from the network) when UPLOAD/
DOWNLOAD
function is selected.

DCS 500

FPROM D35

FPROM D33&34

RAM

Control

Panel

FPROM

DOWNLOAD

UPLOAD

FACTORY-
SET VALUE

FPROM = FLASH-PROM
RAM = Random Access Memory

SAVE MOT1 SET
SAVE MOT2 SET

Parameter 11202:

1 =
2 =

4 =
5 =

SELECT MOT1 SET
SELECT MOT2 SET

Parameter 11202:


If one or both of these functions have been performed additional ac-
tions may be needed. For example BACKUPSTOREMODE should
be selected for saving the values to the backup memory, if a
DOWNLOAD had taken place.

UPLOAD will copy all parameters and connections, which are dif-
ferent to default, from the RAM memory of the drive to the FPROM
memory of the Control Panel CDP 31x.

Before a DOWNLOAD is started the factory-set values (default val-
ues) should be available within the drive´s RAM memory.
Factory-set values are always available in control board memory
and they can be called by means of BACKUPSTOREMODE pa-
rameter 11202 [FACTORY_SET_VALUE] or by means of S2 switch
on the control board SDCS-CON-x.

The DOWNLOAD will copy all values stored in the FPROM memory
of the CDP 31x to the RAM memory of the drive. Downloaded
parameters should be saved to the FPROM memory of the control
board SDCS-CON-x. See chapter 3.5"Saving of Parameters to
backup memory"
.

Note: For reasons of safety the DOWNLOAD function will only
operate

if

LOCAL mode“ of the Control Panel CDP 31x

is

selected!

3ADW000055R0401_DCS500B_Operating Instruction_e_d