Chapter 4 - Signals and Troubleshooting


DCS 500B / DCP 500B Operating Instructions

IV A

4 - 9

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Action

Status

signal

(FAULT_WORD_1/2)

Remark

field weakening range too big / threshold

too high

Check: - Do selection parameters match

the field exciter (field supply)?

- Field exciter, it´s supply, cable and

field winding;

- Take this error message at the data

logger as a trigger condition and

record signals 11302 and 11203

- Status/level of acknowledge signal.

F

40

No ext. FAN ack.

No acknowledge from FAN of motor

Check: - Was input for acknowledge

signal

(parameter

[P 911]

) used?

- Contactor circuit/supply for fan of

motor;

- Status of binary inputs/outputs

(DI/DO) on SDCS-IOB-1/2 board.

11102

bit 6

(1)

F

41

No main cont. ack.

Missing main contactor acknowledge

Check: - Switch-ON/-OFF sequence

correct?

- Status of binary input DI for ac-

knowledge signal and of ACK

MAIN CONT (

[P 912]

) after main

contactor is closed;

- Status of binary output DO resp.

of auxiliary contactor (relay)

closing the main contactor after

ON/OFF

command.

11102

bit 7

(3)

F 42

Field ex.1 not OK

FIELD EXCITER 1 (field supply 1) status is not
O.K.

A fault was found during self-diagnosis of
field exciter {see

[11203]

)}

Check: - Field exciter operation;

change the unit, if necessary.

11102

bit 12

(1)

F 43

Field ex.2 not OK

FIELD EXCITER 2 (field supply 2) status is not
O.K.

{See Fault Code

F 42

}

11102

bit 13

(1)