Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Action

Status

signal

(FAULT_WORD_1/2)

Remark

F 8

Current rise fault

Actual current changed faster than allowed

The rate of current change is monitored.
Check: - Setting of current reference slope

[P406] and CURRENT_RISE_MAX

[P418];

Level and setting of line voltage

and motor voltage; setting of

current controler

11103

bit 10

(2)

S21.232

and

higher

F 14

Speed meas. fault

Speed feedback (measurement) fault

Check: - Incremental encoder and connec-

tion cable, encoder power supply

(feedback might be too low);

- Tacho polarity and voltage

(does a total mismatch exist?)

- Electronic boards SDCS-CON-x,

SDCS-IOB-3, SDCS-POW 1;

- Connection converter – armature

circuit

open?

- Correct setting for selection of

speed feedback monitoring?

11102

bit 5

(3)

F 17

Type coding fault

(Converter) Type coding fault

SDCS-PIN-xx board not connected to board
SDCS-CON-x or SDCS-PIN-xx not coded.
Check: - Flat cables X12 and X13 O.K.?

- Faulty coding on SDCS-PIN-xx?

- Correct coding of unit size

C4?

Note

: This fault signal will be shown, if jumper S2 (on board

SDCS-CON-x) is in position 1–2 while switching ON the elec-
tronics supply. In that case select BACKUP-STOREMODE
[11202], save the paramter set, switch OFF the electronics,
reset jumper S2 and switch ON the electronics again.

11102

bit 8

(1)

Can

not be

reset

F 18

Backup read fault

Backup read fault

(Parameter saving fault)

Cause: Wrong or missing checksum, data error
while writing or reading.

Note

:

T

ry again BACKUP-STORE-MODE; for that purpose

-

Move

jumper

S2 (on board

SDCS-CON-x) to Pos. 1–2

with electronics supply switched OFF;

- Switch ON electronics again;

-

Select

BACKUPSTOREMODE [11202];

- Save default parameter set;

- Switch OFF electronics;

-

Reset

jumper

S2 to ist original position;

- Switch ON electronics again.

If display shows F 18 once again, change SDCS-CON-x
board!

11102

bit 9

(1)

Can

not be

reset