Chapter 4 - Signals and Troubleshooting

IV A

4 - 2

DCS 500B / DCP 500B Operating Instructions

4.2 General messages

The general messages will only be shown on the seven segment
display of the control board SDCS-CON-x.

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition

Remark

8

Not available

Program is not running

(1)

.

Not available

Normal situation, no fault / no alarm signal

L

Not available

Indication while loading another firmware
into the drive

(1) Units should be switched off and on electrically; if fault occurs again, the PCBs SDCS-POW-1 and SDCS-CON-x

have to be checked and if necessary to be changed.


4.3 Starting errors (E)

The starting errors will only be shown on the seven segment display
of the control board SDCS-CON-x.

With starting errors it will not be possible to start the drive.

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition

Remark

E1

Not available

ROM memory test error

(1)

E2

Not available

RAM memory test error

(1)

E3

Not available

No TC-link board
(not valid for software version S21.1xx)

E4

Not available

Communic. board SDCS-COM-x faulty

(2)

E5

Not available

No control program in memory

(3)

E6

Not available

ASIC not O.K.

(1)

E7

Not available

Parameter FLASH identity test failed

(1)

(1) Units should be switched off and on electrically; if fault occurs again, the PCBs SDCS-POW-1 and SDCS-CON-x

have to be checked and if necessary to be changed.

(2) Check communication board, plug in correctly

and if necessary change the board.

(3) Load firmware once more.



3ADW000055R0401_DCS500B_Operating Instruction_e_d