DCS 500 User Manual

Page 64

Advertising
background image

Chapter 4 - Signals and Troubleshooting

IV A

4 - 12

DCS 500B / DCP 500B Operating Instructions

4.5 Alarm Signals (A)

The alarm signals will be shown on the seven segment display of
the control board SDCS-CON-x as codes A . . as well as on the
LCD of the control panel CDP 31x as plain text. Alarm signals will
only be displayed, if there is no fault signal active.

The alarm signals - with the exception of

A 101

and

A 102

- will not

result in switching off the signal 10910 resp. in stopping the drive.

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Possible source

Signal

number

(ALARM_WORD_1/2)

Remark

A 101 Start inhibition

Alarm Start Inhibition

Pin

908

(START_INHIBIT) is set to logical

"1“; drive cannot be switched ON.
When pin is set to logical "0“, the alarm sig-
nal will be reset.

11104

bit 0

A 102 Emergency stop

Alarm EMERGENCY STOP

Pin

906

has a logical "0" level; for signal re-

set, see introductory remarks in Chapter 4.4
"Fault Signals“ and Chapter 3.7 "EMER-
GENCY STOP RESETTING“.

11104

bit 1

A 103 Motor 1 temp. alarm

Alarm Overtemperature

MOTOR 1

Check: - Parameter setting MOT1.TEMP_

ALARM_L

[P 1402]

correct?

See also Fault Code

F 6.

11104

bit 2

A 104 Motor 1 overl.alarm

Alarm Overload

MOTOR 1 (Thermal Model 1)

Check: - See Fault Code

F 7.

11104

bit 3

A 105 Conv. overtemp.

alarm

Alarm Overtemperature

Power Section

This signal will already appear at approx.
10 °C below the shutdown temperature ap-
plying for Fault Signal

F 4

(see

P 10512

).

Check: - See Fault Code

F 4

.

11104

bit 4

A 106 Current reg blocked

Alarm Current Regulator/Controller blocked

Pin 404 (BLOCK) is set to logical "1“.
When pin is set to logical "0“, the alarm sig-
nal will be reset.

11104

bit 5

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Advertising