Chapter 4 - Signals and Troubleshooting


DCS 500B / DCP 500B Operating Instructions

IV A

4 - 7

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Action

Status

signal

(FAULT_WORD_1/2)

Remark

F 28

Armature over-
voltage

Armature (DC circuit) overvoltage

Check: - Setting of param. [

P 511

] suitable

for the system configuration?

- Setting of field current and actual

value as well as the complete

field supply (FIELD EXCITER);

- Was the motor accelerated by

the

load?

-

Speed

scaling;

- Armature voltage feedback;

- Connections between SDCS-

CON-x and SDCS-PIN boards;

- Coding of voltage evaluation on

SDCS-PIN-xx

board.

11101

bit 2

(1)

F 29

Mains undervoltage

Mains supply undervoltage

(AC)

; setting via

parameter

[P 509]

Check: - Does the supply voltage exist?

- Did the mains contactor close?

- Setting of voltage feedback

coding (voltage scaling) correct?

- Connections between SDCS-

CON-x and SDCS-PIN-xx boards;

- Coding of voltage evaluation on

SDCS-PIN-xx

board.

11101

bit 11

(3)

F 30

Mains overvoltage

Mains supply overvoltage (AC)

Mains voltage > 130% of nominal value for
longer than 10s.
Fault tracing see Fault Code

F 29

.

11101

bit 12

(1)

F 31

Not in synchronism

Synchronization fault

(of mains)

Check: - Mains supply, fuses etc.;

- Mains voltage and stability.

11101

bit 13

(3)

F 32

Field ex.1 overcurr

FIELD EXCITER 1 (field supply 1) overcurrent

Check: - Parameters of

FIELD EXCITER 1

;

- Connections of field exciter as

well as insulation level of cable

and of field winding.

11101

bit 14

(1)

F 33

Field ex.1 comerror

FIELD EXCITER 1 communication error

Check: - Flat cable connections X14: or

cable X16: between SDCS-

CON-x board and field exciter;

- Auxil. voltage for ext. field exciter.

11101

bit 15

(1)

3ADW000055R0401_DCS500B_Operating Instruction_e_d