Chapter 4 - Signals and Troubleshooting

IV A

4 - 14

DCS 500B / DCP 500B Operating Instructions

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Possible source

Signal

number

(ALARM_WORD_1/2)

Remark

A 127 Ext. FAN ack.alarm

Alarm No Acknowledge from External FAN (of
Motor)

Check: - See Fault Code

F 40.

11104

bit 15

A 128 Panel disconnected

Alarm No Communication with (Control)
Panel CDP 31x

No communicaiton is possible with the con-
trol Panel CDP 31x in REMOTE mode; the
alarm signal will disappear once communi-
cation is in order again.

11105

bit 0

A 129 Type code changed

Alarm Type Code (Hardware Code of Thyris-
tor Power Converter) changed

Unit type code stored in memory differs from
the hardware coding.
Check: - New control board SDCS-

CON-x?

- Control board SDCS-CON-x /

SDCS-PIN-xx board inter-

changed?

Action: - Save values in non-volatile

memory using BACKUPSTORE-

MODE

[11202]

;

see also Alarm Code

A 130.

11105

bit 1

A 130 Init values read,S2

Alarm Initializiation Values read into RAM

Default values have been loaded into the
RAM, e.g. using Jumper

S2

.

Signal will then often appear in conjunction
with Alarm Code

A 129

; but will not always

be shown on the unit's seven-segment dis-
play, though it will always be entered in the
Fault Logger.

11105

bit 2

A 132 Param set 2 missing

Alarm Valid Parameter Set 2 missing

Check: - Has - before activation of Param-

eter Set 2 (over [

P 913]

or

[P 11202]

) - the content of the

RAM been saved over

[P 11202]

,

Value 5 (SELECT_MOT2_SET)

in Motor Set 2?

11105

bit 3