Chapter 4 - Signals and Troubleshooting

IV A

4 - 20

DCS 500B / DCP 500B Operating Instructions

Para-

meter

Code

/

bit

Text on LCD of con-

trol panel CDP 31x

Definition / explication of the signal

Remark

12

(FIELD2_CURR_MIN_L)

1 = motor 2 field current above min level

11204

-- ---- TC_STATUS:

Status of the torque control sequencing

00

(RDY ON)

1 = ready for closing contractor

01

(MAIN CONT ON)

1 = command to close contractor

02

(RDY RUNNING)

1 = ready for run command

03

(RUNNING)

1 = command to release controllers

04

(TC_RDY_REF)

1 = ready for reference

05

(TC_FIELD_CHANGE)

1 = field reversal is active

06

(CONTINUOUS_CURR)

1 = armature current is discontinuous

11205

-- ---- BC:

Status of the current regulator. If the value of BC is
zero, everything is OK. Otherwise different bits of
BC will indicate the reason for blocking the current
regulator

00

--------

Overcurrent

01

--------

Freewheeling unit was fired

02

--------

field reversal

03

--------

supply system undervoltage

04

--------

12Puls only: fault 65 and 66 occurred

05

--------

12Puls only: signal via cable X18

06

--------

supply system overvoltage

07

--------

type code error

08

--------

suppression of controller at regulator change-over

09

--------

processor overload

10

--------

thyristor diagnostic running

11

-------- --------

12

--------

primary (AC) or secondary (48Vdc) power failure

13

--------

synchronization signal missing

14

--------

pulse firing section not in synchronism

15

--------

not released


3ADW000055R0401_DCS500B_Operating Instruction_e_d