11 PROFIBUS control wiring

Interfacing the pump with the PROFIBUS network is by means of an M12 connector

mounted on a flying lead on the front of the pump.

It is the user’s responsibility to ensure the safe and reliable operation of the pump

under PROFIBUS control.

Note: The transmission speed is limited to a maximum of 1.5Mbit/s.

11.1 PROFIBUS installation

All devices in the bus system must be connected in a line. An IP66 rated T adaptor

should be used to connect the pump to the PROFIBUS line. A maximum of 32 stations

(to include master, slaves and repeaters) are possible and both the beginning and

the end of the cable must be terminated with a terminating resistor.

The M12 socket provided for PROFIBUS installation is IP66 rated. To maintain an

IP66 rated system the PROFIBUS cable, T adaptors and terminating resistors used

must be fitted with IP66 rated M12 industrial connectors.

Note: To prevent low-frequency ground loops, screening which is earthed at one end

should be used. To counter magnetic HF pick-up, shielding earthed at both ends as well as

twisted conductors should be used, this will have no effect against electrical HF pick-up.

The permissible overall length of the bus cabling will vary according to the required

bit rate. If a longer cable or higher bit rate are required repeaters should be used.

The maximum bit rates achievable are shown in the table below.

Bit rate (Kbit/s)

Max. length of type A bus cable (m)

1500

200

500

400

187.5

1000

93.75

1200

19.2

1200

9.6

1200

Note: Total stub length should not exceed 6.6m