8 profibus gsd file – Watson-Marlow Qdos30 User Manual

Page 31

Advertising
background image

Watson-Marlow qdos30 PROFIBUS Pump User Manual

31

The screen will state running or stopped, depending on how the user has set up the

fail-safe function within the PROFIBUS GSD file. The MODE button gives access to

the PROFIBUS settings and the station address. When the menus are accessed, the

pump is still in PROFIBUS bus mode but with no communications. After five minutes

of inactivity the pump will revert back to the home screen and discard any unsaved

changes, if there are still no communications then the BUS ERROR screen will be

displayed.

14.8 PROFIBUS GSD File

The Qdos 30 PROFIBUS pump can be integrated into a PROFIBUS DP V0 network

using a General Station Data (GSD) file. The file identifies the pump and contains

key data including its communication settings, the commands it can receive and the

diagnostic information it can pass to the PROFIBUS master on interrogation.

The GSD file—file name WAMA0E7D.GSD—can be installed from the CDROM supplied

with this pump; or downloaded from the Watson-Marlow website and installed; or

typed into a PROFIBUS master directly from this manual using a GSD editor program.

Note: The data-flow to and from the pump may need to be byte-reversed, due to

differences of handling the data between suppliers of master devices.

The GSD file, filename: WAMA0E7D.GSD

;

;*****************************************************************************

*******

;* ===========================================================================

===== *

;*

*

;* Watson-Marlow Bredel Pumps

*

;* Bickland Water Road

*

;* Falmouth

*

;* Cornwall

*

;* TR11 4RU

*

;* Tel.: +44(1326)370370

*

;* FAX.: +44(1326)376009

*

;*

*

;* ===========================================================================

===== *

;* Filename: WAMA0E7D.GSD

*
;* GSD file version 3 from 2013-09-24