Wcc3.exe screen descriptions, Analog global - averaged list, Analog global averaged list screen – WattMaster WCC III part 4 User Manual

Page 133

Advertising
background image

WCC III Technical Guide

3-129

WCC3.EXE SCREEN DESCRIPTIONS

Mode 1: Averaged List

Value to be averaged

You may input up to 8 analog values to be averaged. The values
may be input in the form of 12A4 (analog input #4 on satellite
controller #12) or GA20 (global analog #20).

If a satellite controller that has an analog input used on this screen
stops communicating, then a value will be missing from the list.
The statement at the bottom of the screen allows you to specify a
default value for the missing values. However, if several inputs are
missing, you may default to a fi xed value. Consider the following
example:

Substitute 72 for each unavailable value until more than 3 values
are unavailable, and then use 70 as the value for this global. If one
analog input on this screen is lost, then 72 will be substituted for
the lost value. If more than 3 analog input values are missing from
this screen, the value of the global will default to 70.

Range

The system has the capability of generating an alarm if the value
of this global analog is either inside or outside of the desired range.
If inside is selected, an alarm will be generated when the value of
the global analog is within the two limits specifi ed. If outside is
selected, an alarm will be generated if the value of the global is
outside the limits specifi ed. Because this is a “choice” fi eld, a list of

ANALOG GLOBAL - AVERAGED LIST

ANALOG GLOBAL #: _20 name is GA 20

Description: Example

Data Pattern: xxx.x

Unit

of

Measure:

1

In Local Set this global defaults to LAST value.

Mode

1:

Averaged

List

Value to be averaged

1A1

1A2

1A3 ----

---- ----

---- ----

Substitute 72.000 for each unavailable value until more than 3 values
are available, then use 70.0 as the value for this global.

---------------

ALARM

---------------

Range

Low Limit

High Limit

Type Message #

Message

None

----

----

0

0

HOME for menu

< Average, Sorted, Integra, Math fu, Lookup, External >

available choices will be displayed at the bottom of the screen:

<

None, Inside, Outside>

You may make your selection by pressing the

<space bar>

until

the desired data pattern has been selected, and then pressing

<Enter>

.

Low Limit

High limit

The Low and High Limits can be either an Address or a Value.
When you move the cursor to this fi eld, the word Address or Value
will appear. Since this is a choice fi eld, press the

<Space Bar>

until the desired choice appears and then press

<Enter>

.

If you select “Value” as the choice for this fi eld, you can enter a
number which will serve as the alarm limit. If you select “Address,”
you can specify an address such as an analog input or global analog
to be used as the alarm limit.

Type

Specifi es the priority (or “importance”) level for any alarms
generated by this input. Alarm types range from one (highest
priority) to eight (lowest priority). The system displays and e-mails
higher priority alarms fi rst. (The fi rst fi ve alarm priorities (1-5)
have e-mail-out-on-alarm capabilities.)

Message #

Specifi es a message number which is used by the system to reference
a message which is entered on the Alarm Message Screen.

Analog Global Screen’s WCC III Logical Address is GAXXX, where GA = Global Analog and XXX = Global Analog Address

Analog Global Averaged List Screen