Wcc3.exe screen descriptions, Dual limit screen, Control output dual limit screen – WattMaster WCC III part 4 User Manual
Page 60

WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-56
Satellite #: _____
Specifi es the number of the satellite you are currently editing. If
you would like to edit a different satellite, use the arrow keys to
move the cursor to this fi eld, enter the desired satellite number,
and press
<Enter>
.
Control Output _____
This fi eld actually contains two separate fi elds. The fi rst fi eld
specifi es the point “type” (i.e., analog input, control output, analog
output, etc.) and displays the current type in textual form. Because
this is a “choice” fi eld, the list of available choices will be displayed
at the bottom of the screen:
<ANALOG INPUT, CONTROL OUTPUT, ANALOG OUTPUT,
TREND LOGGING, LOGIC SWITCH, BINARY OUTPUT>
You may make your selection by pressing the
<space bar>
once
for each choice, until the desired point type has been selected. (If
you select a point type that is different than that currently being
displayed, the screen will be rewritten with the appropriate screen
and data.) The second fi eld specifi es the point number to edit. For
the Control Output Screen, this number can range from one to
eight. If you would like to edit a different point, simply position
the cursor to this fi eld by using the cursor positioning (arrow) keys,
enter the desired point number, and press
<Enter>
.
Mode: ____________
Specifi es the mode type of the output contact. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:
<Undefi ned, EA Driver, Time Clock, Dual Limit>
You may make your selection by pressing the
<space bar>
once
for each choice, until the desired point type has been selected, and
then pressing
<Enter>
. (If you select a mode type that is different
than that currently being displayed, the screen will be rewritten
with the appropriate screen information.)
_______ Contact
Specifi es which of the two available contacts per point (H or C)
to confi gure. Because this is a “choice” fi eld, the list of available
choices will be displayed at the bottom of the screen:
<H,C>
Satellite # 1
CONTROL OUTPUT 1
Mode: Dual Limit
“H” Contact
Description: S1-K1h
Contact Open Message #: 2 Off
Analog Control by: ////
Contact Closed Message #: 1 On
Schedule Control by: 1
Minimum Off Time: 0 Seconds
Alternate Mode selected by: ////
Minimum On Time: 0 Seconds
Override OPEN when 0B2 is OFF
Hysteresis: +/- 0 x 1 DEG.
Low
Limit
Hi
Limit
Local
Set:
OPEN
Between
0
&
0
DEG.
On
Schedule:
OPEN
Between
0
&
0
DEG.
Off Schedule:
OPEN
Between
0
&
0 DEG.
On Schedule: (alt)
OPEN
Between
0
&
0 DEG.
Off Schedule:(alt)
OPEN
Between
0
&
0 DEG.
Data Register is measured from Midpoint and Refl ects Hysteresis
HOME for menu
DUAL LIMIT SCREEN
Control Output Screen’s WCC III Logical Address is XXXKYh or c, where XXX = Satellite Address #, K = Control Output,
Y = Control Output #, h = Heat (General Purpose), and c = Cool (General Purpose)
Control Output Dual Limit Screen